Notice of Violations (Current)
NOV Number:
E0020251009
(Pending)
Issue Date:
4/15/2025
Expiration Date:
6/14/2025
View NOV Form
Tanks |
Violation |
1, 2, 3 |
Line interstitial sensors have been raised and rendered inoperational. - (STP/UDC) Interstitial sensor(s) are not functioning effectively. Place sensors vertically at the lowest point in the sump. (Per Ill Adm. Code 175.410.l.2.A.ii) |
2 |
Open electrical conduit or junction boxes. - Electrical conduit in STP containment is corroded and wires are exposed. |
2 |
Triennial spill prevention equipment testing not completed. |
2 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - STP containment requires testing. |
1, 2, 3 |
Water in dispenser containment with interstitial sensors - Remove water and repair containments to prevent water ingress - Fuel in UDC (disp 5/6), investigate and repair. |
NOV Number:
E0020251010
(Pending)
Issue Date:
4/15/2025
Expiration Date:
6/14/2025
View NOV Form
Tanks |
Violation |
Facility |
Dispensers require collision protection - Bollards are corroded
Provide appropriate collision protection for above referenced dispenser island(s). (Per Ill Adm. Code 175.450.e.13) |