Notice of Violatlions (Current)
NOV Number:
E0020252622
(Pending)
Issue Date:
10/6/2025
Expiration Date:
12/5/2025
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom. |
NOV Number:
E0020252696
(Pending)
Issue Date:
10/6/2025
Expiration Date:
12/5/2025
View NOV Form
| Tanks |
Violations |
| 1, 7 |
Miscellaneous - STP sump lids are very difficult to get off. |
| 1, 2, 3, 4, 5, 6, 7 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
| 2 |
Submit Notification Form for Product Change - Tank 2 is listed as mid-grade whenit's regular. A notification form is required to be completedfor a product change. |
| 1, 2, 3, 7 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Dispenser sumps 7/8 and 9/10 need triannual testing. |
| 1, 2 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - There is water in both STP sumps. Tank 2 sump sensor is in alarm. All water shall be removed and sensor clear of alarms. |