Notice of Violatlions (Current)
NOV Number:
E0020252622
(Pending)
Issue Date:
10/6/2025
Expiration Date:
12/5/2025
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom. |
NOV Number:
E0020252696
(Pending)
Issue Date:
10/6/2025
Expiration Date:
12/5/2025
View NOV Form
| Tanks |
Violations |
| 1, 2, 3, 4, 5, 6, 7 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - This will be completed by 12/16/25. |
| 1, 2, 3, 7 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Dispenser sumps 7/8 and 9/10 need triannual testing. |
NOV Number:
E0020253248
(Pending)
Issue Date:
12/12/2025
Expiration Date:
2/10/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser - 175.210 g) All dispensing units shall be readily visible from the control station without
assistive devices. However, as an alternative, in the event that the attendant's view
of a dispenser is permanently obstructed, or if a dispenser is located so that
activity at the dispenser is not readily visible, closed-circuit cameras that provide
a view of each side of the dispensing unit and project an image on a screen at least
6 inches in diagonal located at the control station may be used. The cameras shall
be allowed to sweep to provide a view of multiple dispensing locations, but must
provide a view on the screen of each dispensing unit at least every 30 seconds. In
lieu of the closed-circuit camera, the facility may elect to have an emergency stop
that shall be located at least 20 and not more than 50 feet from the dispenser that
has a permanently obstructed view. Using an emergency stop in lieu of the closed circuit
camera pursuant to this subsection (g) must be approved in advance by
OSFM. If a closed-circuit camera or viewing screen is inoperable and cannot
provide surveillance of dispensing units to the attendant at the control station, and
an emergency stop has not been approved by OSFM and provided in lieu of the
camera as provided in this subsection (g), self-service dispensing of fuel at these
dispensers is prohibited. |