| Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. |
| Facility |
Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser - Section 175.210g; All dispensing units shall be readily visible from the control station without assistive devices. If view is permanently obstructed, or the dispenser is located so that activity is not readily visible, closed-circuit cameras that provide a view of each side of the dispensing unit and project an image on a screen at least 6 inches in diagonal located at the control station may be used. You may also elect to install an emergency stop switch at least 20 feet but no more than 50 feet from any dispenser with a permanently obstructed view. |
| Facility |
Facility Operation and Maintenance Plan not completed or available. - FORM ON SITE IS NOT UP TO DATE. |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. |
| 1, 2 |
Line leak detection equipment in alarm or failed test, must repair or replace. - Line interstitial sensor(s) in alarm on ATG; Repair/replace sensor(s) as necessary to clear alarm. |
| Facility |
Missing copies of Annual Walkthrough Inspection Report. |
| Facility |
Missing copies of current testing certificates for operator training - Copies of all current Class C testing certificates shall be maintained on file on site. |
| Facility |
Missing copy of emergency instructions or emergency procedures plan - FORM ON SITE IS NOT UP TO DATE WITH CONTACT INFO. |
| Facility |
Missing list of designated Class A/B & C Operators |
| Facility |
Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). |
| 1, 2 |
Tank monitor does not appear to function properly and requires maintenance. - ATG in alarm; repair/replace as necessary to secure alarm. |
| 1, 2 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. |