Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2027733
Status: Active
Facility Name: Central DuPage Hospital
Address: 25 N. Winfield Road
Winfield, IL 60199
County: Du Page
Property Parcel: 04-12-403-034
Facility Type: Private Institution
Owner Type: Private
Green Tag Decal: Z003431
Green Tag Issue Date: 5/15/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Central DuPage Hospital Association
Owner Address: 25 N. Winfield Road
Winfield, IL 60199
Owner Status: Current Owner
Purchase Date: 1/1/1969
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 2/27/2026

Motor Fuel Dispensing Permits

No MFD Permits Found

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0017416 Central DuPage Hospital Association Current Owner 1/1/1969

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00358-2025UPG Upgrade Approved / Issued 3/27/2025 3/27/2025 9/29/2025 Documents
00318-2025INS Install Approved / Issued 3/17/2025 3/18/2025 9/18/2025 Documents

Notice of Violations (Current)

No Notice of Violations Found

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
2024-0936 12/9/2024 Removal Log 00762-2024REM
N/A 5/15/2024 Abandonment Log 00541-2024ABN

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 4/17/1992
OSFM First Notify Date: 8/6/1991 Abandoned Material:
Current Age: 0 Abandoned Date:
Install Date: 1/1/1969 Red Tag Issue Date:
Last Used Date: 3/31/1992 Fee Due: $0.00
Product Date: 7/1/1991

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 700 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/27/1993
OSFM First Notify Date: 8/6/1991 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 1/1/1969 Red Tag Issue Date:
Last Used Date: 10/25/1993 Fee Due: $0.00
Product Date: 1/1/1969

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 5000 Petroleum Use: Consumptive Use on Premises for Heating
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 4/1/1992
OSFM First Notify Date: 1/15/1993 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1969 Fee Due:
Product Date: 1/1/1962

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 10000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Pre 1974 CAS Code:
Regulated Status: Exempt Removed Date:
OSFM First Notify Date: 1/15/1993 Abandoned Material:
Current Age: 58 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1968 Fee Due:
Product Date: 1/1/1967

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 4000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 1/8/2009
OSFM First Notify Date: 4/14/1992 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 7/1/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Double Wall N/A N/A
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Spill Contain Device Manhole Field Constructed
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 10000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/18/1994 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: 3/2/1993 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/2/1993

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping American with Annual Prec Line Testing Suction 8/8/2017 8/8/2018
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 11/13/2024 11/13/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 11/13/2024 11/13/2025
Overfill Prev Device Overfill Drop Tube Valve 11/13/2024 11/13/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 11/13/2024 11/13/2027
Leak Detect - Piping Sump Sensor 11/13/2024 11/13/2025
Piping Single Wall Transition Sump 10/12/2021 10/12/2024
Leak Detect - Piping Sump Sensor 11/13/2024 11/13/2025
Spill Contain Device Single Wall Spill Bucket 11/13/2024 11/13/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping American with Annual Prec Line Testing Suction Functional Pass 11/13/2024
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 1/10/2024
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 4/18/2022



Tank Number 7

Capacity: 600 Petroleum Use: Consumptive Use on Premises for Heating
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: State Removed Date: 8/11/1999
OSFM First Notify Date: 2/2/1994 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 12/23/1993 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/23/1993

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 8

Capacity: 25000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/8/2005 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 10/5/2004 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/15/2005

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping American with Annual Prec Line Testing Suction 8/8/2017 8/8/2018
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 11/13/2024 11/13/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 11/13/2024 11/13/2025
Overfill Prev Device Overfill Alarm 11/13/2024 11/13/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 11/13/2024 11/13/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 10/13/2022 10/13/2023
Leak Detect - Piping Sump Sensor 11/13/2024 11/13/2025
Piping Single Wall Transition Sump 10/12/2021 10/12/2024
Spill Contain Device Single Wall Spill Bucket 11/13/2024 11/13/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping American with Annual Prec Line Testing Suction Functional Pass 11/13/2024
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 1/10/2024
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 8/2/2023



Tank Number 9

Capacity: 20000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 12/9/2024
OSFM First Notify Date: 8/8/2005 Abandoned Material: Inert material mixed with portland cement
Current Age: 19 Abandoned Date: 5/15/2024
Install Date: 9/23/2004 Red Tag Issue Date:
Last Used Date: 10/1/2023 Fee Due: $0.00
Product Date: 7/15/2005

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping American with Annual Prec Line Testing Suction 8/8/2017 8/8/2018
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 10/13/2022 10/13/2023
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 10/13/2022 10/13/2023
Overfill Prev Device Overfill Alarm 10/12/2021 10/12/2024
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 10/12/2021 10/12/2024
Leak Detect - Piping Non-Discriminating Sump Sensor 10/13/2022 10/13/2023
Piping Single Wall Transition Sump 10/12/2021 10/12/2024
Leak Detect - Piping Sump Sensor 10/13/2022 10/13/2023
Spill Contain Device Single Wall Spill Bucket 10/12/2021 10/12/2024
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping American with Annual Prec Line Testing Suction Functional Pass 4/15/2022
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 4/15/2022
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Fail 10/4/2023



Tank Number 10

Capacity: 25000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/23/2010 Abandoned Material:
Current Age: 14 Abandoned Date:
Install Date: 11/16/2010 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Piping American with Annual Prec Line Testing Suction 8/8/2017 8/8/2018
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 11/13/2024 11/13/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 11/13/2024 11/13/2025
Overfill Prev Device Overfill Alarm 11/13/2024 11/13/2027
Overfill Prev Device Overfill Drop Tube Valve 11/13/2024 11/13/2027
Piping Flexible Double Wall NUPI Smartflex N/A N/A
Piping Single Wall STP/Tanktop Sump 11/13/2024 11/13/2027
Leak Detect - Piping Sump Sensor 11/13/2024 11/13/2025
Piping Single Wall Transition Sump 11/13/2024 11/13/2027
Leak Detect - Piping Sump Sensor 11/13/2024 11/13/2025
Spill Contain Device Single Wall Spill Bucket 10/12/2021 10/12/2024
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping American with Annual Prec Line Testing Suction Functional Pass 11/13/2024
Leak Detect - Piping Siphon Bar Functional Pass 11/13/2024
Piping Flexible Double Wall NUPI Smartflex Precision Test (Piping) Pass 1/10/2024
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 3/31/2025



Tank Number 11

Capacity: 25000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/23/2010 Abandoned Material:
Current Age: 14 Abandoned Date:
Install Date: 11/16/2010 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping American with Annual Prec Line Testing Suction 8/8/2017 8/8/2018
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 11/13/2024 11/13/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 11/13/2024 11/13/2025
Overfill Prev Device Overfill Alarm 11/13/2024 11/13/2027
Overfill Prev Device Overfill Drop Tube Valve 11/13/2024 11/13/2027
Piping Flexible Double Wall NUPI Smartflex N/A N/A
Piping Single Wall STP/Tanktop Sump 11/13/2024 11/13/2027
Leak Detect - Piping Sump Sensor 11/13/2024 11/13/2025
Piping Single Wall Transition Sump 11/13/2024 11/13/2027
Leak Detect - Piping Sump Sensor 11/13/2024 11/13/2025
Spill Contain Device Single Wall Spill Bucket 11/13/2024 11/13/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping American with Annual Prec Line Testing Suction Functional Pass 11/13/2024
Piping Flexible Double Wall NUPI Smartflex Precision Test (Piping) Pass 1/10/2024
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 3/31/2025



Tank Number 12

Capacity: 20000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/23/2010 Abandoned Material:
Current Age: 14 Abandoned Date:
Install Date: 11/16/2010 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Piping American with Annual Prec Line Testing Suction 8/8/2017 8/8/2018
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 11/13/2024 11/13/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 11/13/2024 11/13/2025
Overfill Prev Device Overfill Alarm 11/13/2024 11/13/2027
Overfill Prev Device Overfill Drop Tube Valve 11/13/2024 11/13/2027
Piping Flexible Double Wall NUPI Smartflex N/A N/A
Piping Single Wall STP/Tanktop Sump 11/13/2024 11/13/2027
Leak Detect - Piping Sump Sensor 11/13/2024 11/13/2025
Piping Single Wall Transition Sump 11/13/2024 11/13/2027
Leak Detect - Piping Sump Sensor 11/13/2024 11/13/2025
Spill Contain Device Single Wall Spill Bucket 11/13/2024 11/13/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping American with Annual Prec Line Testing Suction Functional Pass 11/13/2024
Leak Detect - Piping Siphon Bar Functional Pass 11/13/2024
Piping Flexible Double Wall NUPI Smartflex Precision Test (Piping) Pass 1/10/2024
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 3/31/2025



Tank Number 13

Capacity: 20000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Installed/Not in Use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/8/2025 Abandoned Material:
Current Age: 0 Abandoned Date:
Install Date: 12/11/2024 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Leak Detect - Piping American with Sensors/No Test Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 4/29/2025 4/29/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/29/2025 4/29/2026
Overfill Prev Device Overfill Alarm 2/27/2025 2/27/2028
Overfill Prev Device Overfill Drop Tube Valve 1/10/2025 1/10/2028
Piping Fiberglass Double Wall N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump 1/10/2025 1/10/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/29/2025 4/29/2026
Spill Contain Device Double Wall Spill Bucket 1/10/2025 1/10/2028
Tank Composite Double Wall Lannon N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping American with Sensors/No Test Suction Functional Pass 4/29/2025
Piping Fiberglass Double Wall Precision Test (Piping) Pass 2/27/2025
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 2/27/2025
Tank Composite Double Wall Lannon Precision Test (Tank) Pass 2/26/2025

Dispenser Information



MFD Motorfuel Dispensing Forms

No Forms Found