Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2027733
Status: Active
Facility Name: Central DuPage Hospital
Address: 25 N. Winfield Road
Winfield, IL 60199
County: Du Page
Property Parcel: 04-12-403-034
Facility Type: Private Institution
Owner Type: Private
Green Tag Decal: X004243
Green Tag Issue Date: 9/21/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Central DuPage Hospital
Owner Address: 25 N. Winfield Road
Winfield, IL 60199
Owner Status: Current Owner
Purchase Date: 1/1/1969
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 2/27/2025

Motor Fuel Dispensing Permits

No MFD Permits Found

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0017416 Central DuPage Hospital Current Owner 1/1/1969

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00250-2024ENT Tank Entry Approved / Issued 3/2/2024 3/4/2024 9/4/2024 Documents

Deficiencies (Current)

NOV Number: E0020231812 (Pending)    Issue Date: 8/9/2023    Expiration Date: 10/8/2023    View NOV Form

Tanks Deficiency
9 Tank interstitial sensor functional test not accomplished (Required annually). - Tank 9 install permit #04876-2004INS states there is a tank sensor. Previous records show there is a sensor also. Sensor must have annual testing performed.

NOV Number: E0020231813 (Pending)    Issue Date: 8/9/2023    Expiration Date: 10/8/2023    View NOV Form

Tanks Deficiency
6, 8, 9, 10, 11, 12 Precision line test required. - Annual presicion line test is required with American Suction.

NOV Number: E0020232227 (Pending)    Issue Date: 10/6/2023    Expiration Date: 12/5/2023    View NOV Form

Tanks Deficiency
9 Miscellaneous - Failed tank interstitial test.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 4/17/1992
OSFM First Notify Date: 8/6/1991 Abandoned Material:
Current Age: 0 Abandoned Date:
Install Date: 1/1/1969 Red Tag Issue Date:
Last Used Date: 3/31/1992 Fee Due: $0.00
Product Date: 7/1/1991

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 700 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/27/1993
OSFM First Notify Date: 8/6/1991 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 1/1/1969 Red Tag Issue Date:
Last Used Date: 10/25/1993 Fee Due: $0.00
Product Date: 1/1/1969

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 5000 Petroleum Use: Consumptive Use on Premises for Heating
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 4/1/1992
OSFM First Notify Date: 1/15/1993 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1969 Fee Due:
Product Date: 1/1/1962

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 10000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Pre 1974 CAS Code:
Regulated Status: Exempt Removed Date:
OSFM First Notify Date: 1/15/1993 Abandoned Material:
Current Age: 57 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1968 Fee Due:
Product Date: 1/1/1967

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 4000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 1/8/2009
OSFM First Notify Date: 4/14/1992 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 7/1/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Double Wall N/A N/A
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Spill Contain Device Manhole Field Constructed
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 10000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/18/1994 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: 3/2/1993 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/2/1993

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping American with Annual Prec Line Testing Suction 1/10/2024 1/10/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 1/10/2024 1/10/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 1/10/2024 1/10/2025
Overfill Prev Device Overfill Drop Tube Valve 10/12/2021 10/12/2024
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 10/12/2021 10/12/2024
Leak Detect - Piping Sump Sensor 1/10/2024 1/10/2025
Piping Single Wall Transition Sump 10/12/2021 10/12/2024
Leak Detect - Piping Sump Sensor 1/10/2024 1/10/2025
Spill Contain Device Single Wall Spill Bucket 10/12/2021 10/12/2024
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 1/10/2024
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 4/18/2022



Tank Number 7

Capacity: 600 Petroleum Use: Consumptive Use on Premises for Heating
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: State Removed Date: 8/11/1999
OSFM First Notify Date: 2/2/1994 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 12/23/1993 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/23/1993

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 8

Capacity: 25000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/8/2005 Abandoned Material:
Current Age: 18 Abandoned Date:
Install Date: 10/5/2004 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/15/2005

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping American with Annual Prec Line Testing Suction 1/10/2024 1/10/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 1/10/2024 1/10/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/11/2024 4/11/2025
Overfill Prev Device Overfill Alarm 10/12/2021 10/12/2024
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 10/12/2021 10/12/2024
Leak Detect - Piping Non-Discriminating Sump Sensor 10/13/2022 10/13/2023
Piping Single Wall Transition Sump 10/12/2021 10/12/2024
Spill Contain Device Single Wall Spill Bucket 10/12/2021 10/12/2024
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 1/10/2024
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 8/2/2023



Tank Number 9

Capacity: 20000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Out of service CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/8/2005 Abandoned Material:
Current Age: 18 Abandoned Date:
Install Date: 9/23/2004 Red Tag Issue Date:
Last Used Date: 10/1/2023 Fee Due: $0.00
Product Date: 7/15/2005

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping American with Annual Prec Line Testing Suction 4/15/2022 4/15/2023
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 10/13/2022 10/13/2023
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 10/13/2022 10/13/2023
Overfill Prev Device Overfill Alarm 10/12/2021 10/12/2024
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 10/12/2021 10/12/2024
Leak Detect - Piping Non-Discriminating Sump Sensor 10/13/2022 10/13/2023
Piping Single Wall Transition Sump 10/12/2021 10/12/2024
Leak Detect - Piping Sump Sensor 10/13/2022 10/13/2023
Spill Contain Device Single Wall Spill Bucket 10/12/2021 10/12/2024
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 4/15/2022
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Fail 10/4/2023



Tank Number 10

Capacity: 25000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/23/2010 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 11/16/2010 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Piping American with Annual Prec Line Testing Suction 1/10/2024 1/10/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 1/8/2024 1/8/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 1/8/2024 1/8/2025
Overfill Prev Device Overfill Alarm 10/12/2021 10/12/2024
Overfill Prev Device Overfill Drop Tube Valve 10/12/2021 10/12/2024
Piping Flexible Double Wall NUPI Smartflex N/A N/A
Piping Single Wall STP/Tanktop Sump 10/12/2021 10/12/2024
Leak Detect - Piping Sump Sensor 1/8/2024 1/8/2025
Piping Single Wall Transition Sump 10/12/2021 10/12/2024
Leak Detect - Piping Sump Sensor 1/8/2024 1/8/2025
Spill Contain Device Single Wall Spill Bucket 10/12/2021 10/12/2024
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall NUPI Smartflex Precision Test Pass 1/10/2024
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 4/18/2022



Tank Number 11

Capacity: 25000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/23/2010 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 11/16/2010 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping American with Annual Prec Line Testing Suction 1/10/2024 1/10/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 1/8/2024 1/8/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 1/8/2024 1/8/2025
Overfill Prev Device Overfill Alarm 10/12/2021 10/12/2024
Overfill Prev Device Overfill Drop Tube Valve 10/12/2021 10/12/2024
Piping Flexible Double Wall NUPI Smartflex N/A N/A
Piping Single Wall STP/Tanktop Sump 10/12/2021 10/12/2024
Leak Detect - Piping Sump Sensor 1/8/2024 1/8/2025
Piping Single Wall Transition Sump 10/12/2021 10/12/2024
Leak Detect - Piping Sump Sensor 1/8/2024 1/8/2025
Spill Contain Device Single Wall Spill Bucket 10/12/2021 10/12/2024
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall NUPI Smartflex Precision Test Pass 1/10/2024
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 4/18/2022



Tank Number 12

Capacity: 20000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/23/2010 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 11/16/2010 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Piping American with Annual Prec Line Testing Suction 1/10/2024 1/10/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 1/8/2024 1/8/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 1/8/2024 1/8/2025
Overfill Prev Device Overfill Alarm 10/12/2021 10/12/2024
Overfill Prev Device Overfill Drop Tube Valve 10/12/2021 10/12/2024
Piping Flexible Double Wall NUPI Smartflex N/A N/A
Piping Single Wall STP/Tanktop Sump 10/12/2021 10/12/2024
Leak Detect - Piping Sump Sensor 1/8/2024 1/8/2025
Piping Single Wall Transition Sump 10/12/2021 10/12/2024
Leak Detect - Piping Sump Sensor 1/8/2024 1/8/2025
Spill Contain Device Single Wall Spill Bucket 10/12/2021 10/12/2024
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall NUPI Smartflex Precision Test Pass 1/10/2024
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 4/18/2022

Dispenser Information



MFD Motorfuel Dispensing Forms

No Forms Found