Notice of Violations (Current)
NOV Number:
E0020250324
(Pending)
Issue Date:
2/6/2025
Expiration Date:
4/7/2025
View NOV Form
Tanks |
Violation |
6, 7, 8, 9, 10 |
Piping interstitial must be open in all sumps - All dispensers need the interstice opened.
175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps. |
Facility |
Submit Notification Form for Facility Information Change - This facility is still listed as Bucky's Express #6544 in the OSFM portal. Please submit a notification form changing facility name. |