Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2027486
Status: Active
Facility Name: BP
Address: 21102 Governors Highway Matteson, IL 60443
County: Cook
Property Parcel: 31-22-401-013-000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: AA00293
Green Tag Issue Date: 4/23/2025
Green Tag Expiration Date: 12/31/2027

Owner Details

Owner Name: Matteson BP Inc.
Owner Address: 21102 Governors Highway Matteson, IL 60443
Owner Status: Current Owner
Purchase Date: 5/28/2025
Type of Financial Responsibility:
Financial Responsibility Reporting Due Date:

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 4/23/2025 12/31/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041640 Matteson BP Inc. Current Owner 5/28/2025
U0035738 B&S, Inc. Former Owner 1/28/2010
U0035189 PAV 2, LLC, Former Owner 1/22/2009
U0000575 Amoco Oil Co Former Owner 12/31/1967
U0027493 Amoco Oil Company Former Owner
U0000552 BP Products North America, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252623 (Pending)    Issue Date: 10/3/2025    Expiration Date: 12/2/2025    View NOV Form

Tanks Violations
3 Annual electronic line leak detector test not completed. - Past due 6/20/2025
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs and dispensers. Form can be found at https://sfm.illinois.gov to download and complete.
1, 2, 3 Annual leak detection certification not completed (Required annually). - (ATG Cert.) Past due 6/20/2025
Facility Financial responsibility must be reported yearly - Note: Submit this only after the Change of ownership form is appoved. Financial Responsibility must be declared annually. The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough shall be performed by a licensed contractor shall be conducted and documentation maintained on site.
1, 2, 3 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Past due 4/26/2025
1, 2, 3 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Go to https://sfm.illinois.gov to print out the Shear Valve inspection form.
Facility Submit Notification Form For Ownership Change - The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. Select “New Owner” as the type of notification form. ( Make sure you write down the access Code that is given to you when you start the notification form.)
1, 2, 3 Triennial spill prevention equipment testing not completed. - Past due 4/26/2025

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/15/1991 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 7/19/1990 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 4/26/2023 4/26/2026
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 4/26/2023 4/26/2026
Leak Detect - Piping Electronic Pressurized Line Leak Detection 10/6/2025 10/6/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 10/6/2025 10/6/2026
Overfill Prev Device Overfill Drop Tube Valve 10/6/2025 10/6/2028
Piping Galvanized Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 10/6/2025 10/6/2028
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Galvanized Steel Single Wall Piping Precision Test (Piping) Pass 3/10/2025
Tank STIP3 Single Wall Precision Test (Tank) Pass 2/21/2024



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/15/1991 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 7/19/1990 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 4/26/2023 4/26/2026
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 4/26/2023 4/26/2026
Leak Detect - Piping Mechanical Other Non-vented check valve N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 10/6/2025 10/6/2026
Overfill Prev Device Overfill Drop Tube Valve 4/26/2022 4/26/2025
Piping Galvanized Steel Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 10/6/2025 10/6/2028
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Galvanized Steel Single Wall Piping Precision Test (Piping) Pass 7/17/2021
Tank STIP3 Single Wall Precision Test (Tank) Pass 2/21/2024



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/15/1991 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 7/19/1990 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 4/26/2023 4/26/2026
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 4/26/2023 4/26/2026
Leak Detect - Piping Electronic Pressurized Line Leak Detection 10/6/2025 10/6/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 10/6/2025 10/6/2026
Overfill Prev Device Overfill Drop Tube Valve 4/26/2022 4/26/2025
Piping Galvanized Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 10/6/2025 10/6/2028
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank STIP3 Single Wall Precision Test (Tank) Pass 2/21/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found