Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2027325
Status: Active
Facility Name: XPO Logistics Freight, Inc. - XMD
Address: 957 Tower Rd Mundelein, IL 60060
County: Lake
Property Parcel: 11-31-402-003
Facility Type: Trucking Company
Owner Type: Private
Green Tag Decal: Y003834
Green Tag Issue Date: 2/23/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: XPO Logistics Freight, Inc.
Owner Address: 2211 Old Earhart Rd., Suite 100 Ann Arbor, MI 48105
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 4/14/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 2/23/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038082 XPO Logistics Freight, Inc. Current Owner
U0030862 Con-Way Transportation Service Former Owner 8/7/2002
U0001246 Partners, LB Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251981 (Pending)    Issue Date: 8/7/2025    Expiration Date: 10/6/2025    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
2 Dispensers - hoses cracked, split or worn and require replacement
2 Line interstitial sensor functional test not accomplished (Required annually). - STP sensor failed annual testing
Facility Miscellaneous - Emergency stop shall be conspicuously marked by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters. (Per 41 Ill Admin code 175.210(d)(3))
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom.
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures plan shall be maintained on site for viewing and reference as necessary (See Operator Training Rules 176.645). The emergency plan template is available on the OSFM website.
Facility Missing copy of written UST facility operation & maintenance plan - Adopt and implement a written operations and maintenance plan, signed by both the owner and either a Class A or Class B Operator designated for the UST facility An Operations & Maintenance template is available at www.sfm.illinois.gov to download and complete O & M template and maintain completed form on site.
2 Monthly line interstitial sensor records not available.
2 Overfill alarm does not appear to function properly. - Overfill alarm failed tri-annual testing.
2 Required monthly tank interstitial sensor records not available.
2 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
2 Tank precision test required. - Precision tank test is required due to missing or failed monthly monitoring (Per 41 Ill Admin code 175.630(c)(2))

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
07-1516 11/14/2007 Removal Log 01582-2007REM

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Diesel Fuel Removed Federal $0.00 11/14/2007 - REM
2 20000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1 Active
1 Slave Active
2 Active
2 Slave Active

MFD Motorfuel Dispensing Forms