Notice of Violations (Current)
NOV Number:
E0020252859
(Referred to Legal)
Issue Date:
10/27/2025
Expiration Date:
12/26/2025
View NOV Form
| Tanks |
Violations |
| 1 |
Annual leak detection certification not completed (Required annually). - Last test was 3-29-24 |
| 1 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Street plate cover for piping |
| Facility |
Financial responsibility must be reported yearly - NON COMPLIANT |
| 1 |
Precision line test required. - Last test was 6-5-24 |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
15000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
2/28/1991 |
|
Abandoned Material: |
|
| Current Age: |
44 |
|
Abandoned Date: |
|
| Install Date: |
2/28/1982 |
|
Red Tag Issue Date: |
1/5/2026 |
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
American with Annual Prec Line Testing Suction |
No passing test found |
No passing test found |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 300c with CSLD |
1/21/2026 |
1/21/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
9/22/2023 |
9/22/2026 |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
9/22/2023 |
9/22/2026 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Leak Detect - Piping
|
American with Annual Prec Line Testing Suction
|
Functional
|
Pass
|
1/21/2026
|
|
Piping
|
Flexible Double Wall
|
Precision Test (Piping)
|
Pass
|
1/21/2026
|
|
Tank
|
Fiberglass Single Wall
|
Precision Test (Tank)
|
Pass
|
6/5/2024
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found