Notice of Violations (Current)
NOV Number:
E0020262372
(Pending)
Issue Date:
10/6/2026
Expiration Date:
12/5/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h) |
| 8 |
Mechanical line leak detector requires annual functional test. - Test expired on 09/09/2026 for equipment: Leak Detect - Piping - Mechanical Pressurized Line Leak Detection North |
| 5, 6, 7, 8 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
| 5, 6, 7, 8 |
Tank monitor does not appear to function properly and requires maintenance. - L1 L2 L3 and L5 are is showing that they are in alarm on tank monitor but do not show up on the tape when printed. Says sensor normal. Repair/Replace to fix alarm. |