Notice of Violatlions (Current)
NOV Number:
E0020252780
(Pending)
Issue Date:
10/21/2025
Expiration Date:
12/20/2025
View NOV Form
| Tanks |
Violations |
| 7, 8 |
Miscellaneous - STP Sumps shall be maintaned clean and dry. |
| 9 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to
the environment when the transfer hose is detached from the fill
pipe (e.g., a spill catch basin). Spill containment equipment shall
be maintained in a dry, clean state. |
NOV Number:
E0020252784
(Pending)
Issue Date:
10/21/2025
Expiration Date:
12/20/2025
View NOV Form
| Tanks |
Violations |
| Facility |
Code complying instruction/warning signs are not properly mounted at each dispenser island - Warning signs are required on truck side. Dispensers 9/10, 10Sat/11, and 11Sat.
175.220 a) Minimum signage requires letters shall not be less than 7/8” in height. The top of the sign shall be mounted no higher than 10’ above grade. The wording shall include a minimum of 1) “Warning” 2) “Stop Engine” 3) “No Smoking” 4) “Persons fueling vehicles shall remain with their vehicle, at the nozzle, while fueling is in progress” 5) “It is unlawful and dangerous for anyone to dispense gasoline into unapproved containers” |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom does not work for dispenser 11.
175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom. |