Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2026339
Status: Active
Facility Name: RT 59 Gasoline, Inc.
Address: 1100 West Stearns Road
Bartlett, IL 60103
County: Du Page
Property Parcel: 01-04-401-029
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002778
Green Tag Issue Date: 6/28/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: RT 59 Real Estate, LlC
Owner Address: 1100 W. Stearns Road
Bartlett, IL 60103
Owner Status: Current Owner
Purchase Date: 3/12/2020
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 4/23/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 6/28/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039839 RT 59 Real Estate, LlC Current Owner 3/12/2020
U0034964 Patel, Hemant Former Owner 9/4/2008
U0027493 Amoco Oil Company Former Owner 11/22/1997
U0000552 BP Products North America, Inc. Former Owner 11/22/1997
U0023834 BP Amoco Former Owner 3/30/1995

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00356-2025UPG Upgrade Approved / Issued 3/26/2025 3/26/2025 9/26/2025 Documents

Notice of Violations (Current)

NOV Number: E0020250779 (Pending)    Issue Date: 3/25/2025    Expiration Date: 5/24/2025    View NOV Form

Tanks Violation
5 Ball float vent valve(s) failed inspection; remove ball float vent valve(s). - Per Midwest Tank Testing, LLC the ball float is missing. A new form of over fill is required to be installed. Passing test results shall be entered on nOSFM portal.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
01-1657 Eligible 5/23/2005 6/23/2005 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 9/28/2001
OSFM First Notify Date: 3/6/1989 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 1/1/1989 Red Tag Issue Date:
Last Used Date: 9/14/2001 Fee Due: $0.00
Product Date: 2/14/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 9/28/2001
OSFM First Notify Date: 3/6/1989 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 1/1/1989 Red Tag Issue Date:
Last Used Date: 9/14/2001 Fee Due: $0.00
Product Date: 2/14/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 9/28/2001
OSFM First Notify Date: 3/6/1989 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 1/1/1989 Red Tag Issue Date:
Last Used Date: 9/14/2001 Fee Due: $0.00
Product Date: 2/14/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 15000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/3/2002 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 10/5/2001 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/19/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/24/2025 3/24/2026
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/24/2025 3/24/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 3/24/2025 3/24/2026
Overfill Prev Device Ball Float Vent Valve OPW 30MV 3/24/2025 3/24/2028
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 10/7/2024 10/7/2027
Leak Detect - Piping Sump Sensor 3/24/2025 3/24/2026
Spill Contain Device Single Wall Spill Bucket 10/7/2024 10/7/2027
Tank Fiberglass Brine Filled Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Environ Geo Flex Precision Test (Piping) Pass 3/24/2025
Tank Fiberglass Brine Filled Double Wall Precision Test (Tank) Pass 3/4/2021



Tank Number 5

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/3/2002 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 10/5/2001 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/19/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/24/2025 3/24/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 3/24/2025 3/24/2026
Overfill Prev Device Overfill Drop Tube Valve 3/26/2025 3/26/2028
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 10/7/2024 10/7/2027
Leak Detect - Piping Sump Sensor 3/24/2025 3/24/2026
Spill Contain Device Single Wall Spill Bucket 10/7/2024 10/7/2027
Tank Fiberglass Brine Filled Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Environ Geo Flex Precision Test (Piping) Pass 5/6/2020
Piping Flexible Double Wall Environ Geo Flex Precision Test (Piping) Pass 2/23/2021
Piping Flexible Double Wall Environ Geo Flex Precision Test (Piping) Pass 3/24/2025
Tank Fiberglass Brine Filled Double Wall Precision Test (Tank) Pass 3/4/2021



Tank Number 6

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/3/2002 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 10/5/2001 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/19/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/24/2025 3/24/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 3/24/2025 3/24/2026
Overfill Prev Device Ball Float Vent Valve OPW 30MV 3/24/2025 3/24/2028
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 10/7/2024 10/7/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 3/28/2022 3/28/2023
Leak Detect - Piping Sump Sensor with positive shutdown 3/24/2025 3/24/2026
Spill Contain Device Single Wall Spill Bucket 10/7/2024 10/7/2027
Tank Fiberglass Brine Filled Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Environ Geo Flex Precision Test (Piping) Pass 3/24/2025
Tank Fiberglass Brine Filled Double Wall Precision Test (Tank) Pass 3/4/2021



Tank Number 7

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/3/2002 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 10/5/2001 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/19/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/24/2025 3/24/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 3/24/2025 3/24/2026
Overfill Prev Device Overfill Drop Tube Valve 10/2/2023 10/2/2026
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 10/7/2024 10/7/2027
Leak Detect - Piping Sump Sensor 3/24/2025 3/24/2026
Spill Contain Device Double Wall Spill Bucket 10/7/2024 10/7/2027
Tank Fiberglass Brine Filled Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Environ Geo Flex Precision Test (Piping) Pass 3/24/2025
Tank Fiberglass Brine Filled Double Wall Precision Test (Tank) Pass 3/4/2021

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 10/7/2024 10/7/2027
Leak Detect - Piping Sump Sensor 3/24/2025 3/24/2026



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 10/7/2024 10/7/2027
Leak Detect - Piping Sump Sensor 3/24/2025 3/24/2026



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 10/7/2024 10/7/2027
Leak Detect - Piping Sump Sensor 3/24/2025 3/24/2026



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 10/7/2024 10/7/2027
Leak Detect - Piping Sump Sensor 3/24/2025 3/24/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 10/7/2024 10/7/2027
Leak Detect - Piping Sump Sensor 3/24/2025 3/24/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 10/7/2024 10/7/2027
Leak Detect - Piping Sump Sensor 3/24/2025 3/24/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 10/7/2024 10/7/2027
Leak Detect - Piping Sump Sensor 3/24/2025 3/24/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 10/7/2024 10/7/2027
Leak Detect - Piping Sump Sensor 3/24/2025 3/24/2026



Name\ID Diesel

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 10/7/2024 10/7/2027
Leak Detect - Piping Sump Sensor 3/24/2025 3/24/2026

MFD Motorfuel Dispensing Forms