Notice of Violatlions (Current)
NOV Number:
E0020252467
(Pending)
Issue Date:
9/22/2025
Expiration Date:
11/21/2025
View NOV Form
Tanks |
Violations |
Facility |
Code complying instruction/warning signs are not properly mounted at each dispenser island - Minimum signage is not up to code. Reference 175.210 o) |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h) |
NOV Number:
E0020252468
(Pending)
Issue Date:
9/22/2025
Expiration Date:
11/21/2025
View NOV Form
Tanks |
Violations |
7, 8, 9 |
Line interstitial sensors have been raised and rendered inoperational. - (Dispensers 1-4) Repair/replace sensor(s) into proper location so that it can function as designed. |
4 |
Miscellaneous - Each loading pipe or fill pipe riser shall be identified by color code or labeling to
indicate the product contained in the tank. Reference 175.445 d) |
8 |
Miscellaneous - Equipment in disrepair Reference 176.410 All equipment and other items shall be maintained in accordance with 41 Ill. Adm. Code 174 through 176 and manufacturer's instructions and otherwise shall be kept in good operating condition at all times. |
4, 7, 8, 9 |
Piping interstitial must be open in all sumps - Product piping test boots need pulled back or sharder valves need to be removed after testing to allow the interstice to be open to the sump sensors. 175.420 b)(All dispensers and RUL, PUL, and DSL STP's) |