Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2024739
Status: Active
Facility Name: RichLee Vans, Inc.
Address: 1030 Rural Street Aurora, IL 60506
County: Kane
Property Parcel:
Facility Type: Private Institution
Owner Type: Private
Green Tag Decal: Z000178
Green Tag Issue Date: 8/15/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Fleet

Owner Details

Owner Name: Cook-Illinois Corp.
Owner Address: 2100 Clearwater Drive Oak Brook, IL 60523
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 3/31/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038028 Cook-Illinois Corp. Current Owner
U0012720 Richlee Vans, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020261756 (Pending)    Issue Date: 7/8/2026    Expiration Date: 9/6/2026    View NOV Form

Tanks Violations
Facility Facility Operation and Maintenance Plan not completed or available. - Operations and Maintenance Template needs to be updated and kept on site. https://sfm.illinois.gov/
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30 day walkthroughs are required to be performed and documented on OSFM 30 Day Walkthrough Form which can be found at https://sfm.illinois.gov/
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures Plan needs to be updated and kept on site. https://sfm.illinois.gov/
Facility Missing list of designated Class A/B & C Operators - A/B Operator needs to be on list.
3, 4 Monthly line interstitial sensor records not available. - 2 years of monthly line interstitial records are required to be kept on site.
4 Open electrical conduit or junction boxes. - Junction box cover corroded away. Replace so electric is sealed.
3, 4 Precision line test required. - 2 years of monthly line interstitial records are not available a precision line test is required.
3, 4 Precision tank test required. - 2 years of monthly tank interstitial records are not available a precision tank test is required.
3, 4 Required monthly tank interstitial sensor records not available. - 2 years of monthly tank interstitial records are required to be kept on site.
Facility Submit Notification Form for Ownership Change - The Notification Form is available at: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of an ownership change.
3, 4 Tank monitor does not appear to function properly and requires maintenance. - ATG shows probe out for both tanks. Repair so probes are functioning and alarm is cleared. T4 probe well probe wire is disconnected.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 9/28/1988
OSFM First Notify Date: 9/21/1988 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 11/1/1982 Red Tag Issue Date:
Last Used Date: 9/28/1988 Fee Due: $0.00
Product Date:

Equipment Information

No Equipment Listed


Additional Tests

No Tests Listed




Tank Number 2

Capacity: 1000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 9/28/1988
OSFM First Notify Date: 9/21/1988 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 11/1/1982 Red Tag Issue Date:
Last Used Date: 9/28/1988 Fee Due: $0.00
Product Date:

Equipment Information

No Equipment Listed


Additional Tests

No Tests Listed




Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/15/1999 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 11/1/1988 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/7/2026 8/7/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 7/17/2025 7/17/2026
Overfill Prev Device Overfill Drop Tube Valve 7/5/2024 7/5/2027
Piping Fiberglass Double Wall Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 7/5/2024 7/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown 7/5/2024 7/5/2027
Spill Contain Device Single Wall Spill Bucket 7/5/2024 7/5/2027
Tank Fiberglass Double Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 8/7/2026
Tank Fiberglass Double Wall Precision Test (Tank) Pass 7/5/2024



Tank Number 4

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/15/1999 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 11/1/1988 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/7/2026 8/7/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 7/17/2025 7/17/2026
Overfill Prev Device Overfill Drop Tube Valve 7/5/2024 7/5/2027
Piping Fiberglass Double Wall Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 7/5/2024 7/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown 7/5/2024 7/5/2027
Spill Contain Device Single Wall Spill Bucket 7/5/2024 7/5/2027
Tank Fiberglass Double Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 8/7/2026
Tank Fiberglass Double Wall Precision Test (Tank) Pass 7/5/2024

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump Not applicable Not applicable



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump Not applicable Not applicable

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


MFD Motorfuel Dispensing Forms

No Forms Found