Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2024739
Status: Active
Facility Name: RichLee Vans, Inc.
Address: 1030 Rural Street Aurora, IL 60506
County: Kane
Property Parcel:
Facility Type: Private Institution
Owner Type: Private
Green Tag Decal: Z000178
Green Tag Issue Date: 8/15/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Fleet

Owner Details

Owner Name: Cook-Illinois Corp.
Owner Address: 2100 Clearwater Drive Oak Brook, IL 60523
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 3/31/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038028 Cook-Illinois Corp. Current Owner
U0012720 Richlee Vans, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020261756 (Pending)    Issue Date: 7/8/2026    Expiration Date: 9/6/2026    View NOV Form

Tanks Violations
Facility Facility Operation and Maintenance Plan not completed or available. - Operations and Maintenance Template needs to be updated and kept on site. https://sfm.illinois.gov/
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30 day walkthroughs are required to be performed and documented on OSFM 30 Day Walkthrough Form which can be found at https://sfm.illinois.gov/
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures Plan needs to be updated and kept on site. https://sfm.illinois.gov/
Facility Missing list of designated Class A/B & C Operators - A/B Operator needs to be on list.
3, 4 Monthly line interstitial sensor records not available. - 2 years of monthly line interstitial records are required to be kept on site.
4 Open electrical conduit or junction boxes. - Junction box cover corroded away. Replace so electric is sealed.
3, 4 Precision line test required. - 2 years of monthly line interstitial records are not available a precision line test is required.
3, 4 Precision tank test required. - 2 years of monthly tank interstitial records are not available a precision tank test is required.
3, 4 Required monthly tank interstitial sensor records not available. - 2 years of monthly tank interstitial records are required to be kept on site.
Facility Submit Notification Form for Ownership Change - The Notification Form is available at: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of an ownership change.
3, 4 Tank monitor does not appear to function properly and requires maintenance. - ATG shows probe out for both tanks. Repair so probes are functioning and alarm is cleared. T4 probe well probe wire is disconnected.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 12000 Gasoline Removed Federal $0.00 09/28/1988 - REM
2 1000 Diesel Fuel Removed Federal $0.00 09/28/1988 - REM
3 12000 Diesel Fuel Currently in use Federal $0.00
4 12000 Gasoline - Regular Currently in use Federal $0.00


Dispenser Information

Name\ID Status
1/2 Active
3/4 Active


MFD Motorfuel Dispensing Forms

No Forms Found