Notice of Violations (Current)
NOV Number:
E0020252102
(Referred to Legal)
Issue Date:
8/14/2025
Expiration Date:
10/13/2025
View NOV Form
| Tanks |
Violations |
| 1 |
Annual leak detection certification not completed (Required annually). - Annual leak detection testing shall be performed and passing results entered on OSFM portal. |
| 1 |
Sacrificial system failed test; must repair. - 175.510 f)2)A)i) Sacrificial anodes shall be tested every 3 years as long as
testing results are -850 millivolts or a higher negative
number. In the event testing results do not meet the -850
millivolt requirement, the anodes shall be replaced. This
requirement applies to all sacrificial anodes, including
wristband and spike anodes. |
NOV Number:
E0020260147
(Referred to Legal)
Issue Date:
1/21/2026
Expiration Date:
3/22/2026
View NOV Form
| Tanks |
Violations |
| 1 |
Failed to Empty the Tank to 1" or Less |
| 1 |
Submit Notification Form For OOS Tank Status Change - The Notification Form is available at: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of a tank status change. |
NOV Number:
E0020262453
(Pending)
Issue Date:
10/28/2026
Expiration Date:
12/27/2026
View NOV Form
| Tanks |
Violations |
| 1 |
Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - TANK LEAK DETECTION WAS LAST TESTED ON 7/9/2024, TANK CORROSION PROTECTION FAILED ON 1/10/2025. |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
1000 |
|
Petroleum Use: |
Back-up Generator |
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Condemned Tank |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
4/3/1989 |
|
Abandoned Material: |
|
| Current Age: |
37 |
|
Abandoned Date: |
|
| Install Date: |
12/15/1988 |
|
Red Tag Issue Date: |
1/21/2026 |
| Last Used Date: |
8/14/2025 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
STIP3 Cathodic Protection with Dielectric Coating |
4/27/2021 |
4/27/2024 |
|
Leak Detect - Piping
|
European with No Test Req Suction |
Not applicable |
Not applicable |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 300c with CSLD |
7/9/2024 |
7/9/2025 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
1/3/2025 |
1/3/2028 |
|
Piping
|
Flexible Double Wall Total Containment Enviroflex non-corrosive |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
No passing test found |
No passing test found |
|
Spill Contain Device
|
Single Wall Spill Bucket |
1/3/2025 |
1/3/2028 |
|
Tank
|
STIP3 Single Wall |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found