| 3 |
Line interstitial sensors have been raised and rendered inoperational. - (STP) Interstitial sensor(s) are not functioning effectively. Place sensors vertically at the lowest point in the sump. (Per Ill Adm. Code 175.410(l)(2)(A)(ii)) |
| 1, 2, 3, 4 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - The violation was not complied within 60 days from the initial notice of violation. |
| 1, 2, 3, 4 |
Triennial spill prevention equipment testing not completed. - The violation was not complied within 60 days from the initial notice of violation. |
| 1, 2, 3, 4 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Missing STP & UDC triannual testing. |
| 3 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - STP sump(s) contain(s) liquid. Remove liquid and repair containment to prevent further liquid ingress. Must show documentaion showing repairs completed. (Per 41 Ill Admin code 175.410(h)) |