Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2024479
Status: Active
Facility Name: Thornton Oil Corp. #003
Address: 7600 W. 159th Street
Orland Park, IL 60462
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003061
Green Tag Issue Date: 10/23/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Thorntons, LLC
Owner Address: 2600 James Thornton Way
Louisville, KY 40245
Owner Status: Current Owner
Purchase Date: 2/11/2019
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 2/18/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 12/6/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039521 Thorntons, LLC Current Owner 2/11/2019
U0014995 Thornton's, Inc. - DO NOT USE THIS OWNER ID Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250494 (Pending)    Issue Date: 2/26/2025    Expiration Date: 4/27/2025    View NOV Form

Tanks Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs and dispensers. Form can be found at https://sfm.illinois.gov to download and complete.
Facility Miscellaneous - Each emergency stop shall be identified by an approved sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters. Reference 175.210 d)3) (Outside Emergency stop)
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site.
1, 2, 3, 4, 5, 6 Monthly line interstitial sensor records not available. - Maintain one NORMAL report per LINE, per month, from ATG. (Sensor Status)
1, 2, 4, 5, 6 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Triennial inspection of overfill device (drop tube valve) has not been completed. Testing shall be completed and submitted to OSFM.
1, 2, 3, 4, 5, 6 Piping interstitial must be open in all sumps - Dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. 175.420 b) (All Dispensers)
6 Required monthly tank interstitial sensor records not available. - Maintain one NORMAL report per TANK, per month, from ATG. (Sensor Status)
1, 2, 3, 4, 5 Required monthly tank leak test records not available. - Maintain one PASSING report per TANK, per month, from ATG. Reference 175.630 c)2)B) (CSLD)
1, 2, 3, 4, 5, 6 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Go to https://sfm.illinois.gov to print out the Shear Valve inspection form.
1, 2, 3, 4, 5 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Debris needs to be cleanded out.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 12000 Gasoline - Regular Currently in use Federal $0.00
2 12000 Gasoline - Regular Currently in use Federal $0.00
3 12000 Gasoline - Premium Currently in use Federal $0.00
4 6000 Diesel Fuel Currently in use Federal $0.00
5 6000 Diesel Fuel Currently in use Federal $0.00
6 12000 E85 Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active

MFD Motorfuel Dispensing Forms