Notice of Violations (Current)
NOV Number:
E0020250954
(Pending)
Issue Date:
4/9/2025
Expiration Date:
6/8/2025
View NOV Form
| Tanks |
Violations |
| 1 |
Failed to Empty the Tank to 1" or Less - Per 175.810(a)(1), when placing tanks out of service, the tank and lines must be emptied immediately. The UST is considered empty when all materials have been removed to one inch or less. |
| Facility |
Financial responsibility must be reported yearly - Copy and paste in remarks: Per 41 Ill. Adm. Code 176.220, tank owners/operators must submit an electronic Financial Responsibility Report form on an annual basis. Financial Responsibility must be maintained until the tank is removed or properly abandoned in place by a licensed UST decommissiong contractor. The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility. |
| 1 |
Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - Single walled tank was taken out of service in 2007. Per 175.810(e) tank must be removed as it is condemned. Here is a link to the licensed UST Decommissioning contractors, that can perform UST tank removals: https://webapps.sfm.illinois.gov/ustsearch/ContractorSearch.aspx |
| Facility |
Submit Notification Form for Ownership Change - Per 41 Ill. Adm. Code 176.440 (g), a change of ownership information must be reported on an electronic Notification for Underground Storage Tank form, within 30 days of the change. According to the Cook County Clerkâs Recorder of Deeds Office, a Warranty Deed was recorded on 07/20/07. The Notification Form is available at: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
1100 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Condemned Tank |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
4/7/1987 |
|
Abandoned Material: |
|
| Current Age: |
47 |
|
Abandoned Date: |
|
| Install Date: |
4/7/1979 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/1/2007 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Tank
|
Steel Single Wall |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found