| 4, 5, 6 |
Line interstitial sensors have been raised and rendered inoperational. - STP sensors have been raised.
175.640 a) 2) All new and existing sump sensors must be installed so as to detect liquid per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump. |
| 4 |
Miscellaneous - ATG is in alarm. L2 Fuel Alarm, L4 Fuel Alarm, and L13 High Liquid Alarm |
| 4 |
Miscellaneous - UDC sensors are lying down in UDC sumps. |
| 5 |
Miscellaneous - ATG is in alarm. L2 Fuel Alarm, L4 Fuel Alarm, and L13 High Liquid Alarm |
| 5 |
Miscellaneous - ATG shows 15 gallons .95 of water. |
| 5 |
Miscellaneous - In STP sump there is a drop tube that is missing a cover. |
| 5 |
Miscellaneous - UDC sensors are lying down in UDC sumps. |
| 6 |
Miscellaneous - ATG is in alarm. L2 Fuel Alarm, L4 Fuel Alarm, and L13 High Liquid Alarm |
| 6 |
Miscellaneous - UDC sensors are lying down in UDC sumps. |
| 4, 6 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to
the environment when the transfer hose is detached from the fill
pipe (e.g., a spill catch basin). Spill containment equipment shall
be maintained in a dry, clean state. |
| 4, 5, 6 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Dispensers 5/6, 9/10,19/20, and T6 Regular STP sump have liquid in the sumps. Remove water. |