Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2023371
Status: Active
Facility Name: West Chicago Citgo
Address: 250 S. Neltnor Blvd.
West Chicago, IL 60185
County: Du Page
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003363
Green Tag Issue Date: 11/29/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Amirali Sayani
Owner Address: 1100 Chetwood Drive
Carol Stream, IL 60188
Owner Status: Current Owner
Purchase Date: 11/1/1984
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 7/5/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 9/12/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0031445 Sayani, Amirali Current Owner 11/1/1984
U0013462 Shah, Nadir Former Owner 6/1/2007

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250313 (Pending)    Issue Date: 2/5/2025    Expiration Date: 4/6/2025    View NOV Form

Tanks Violation
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom.

NOV Number: E0020250314 (Pending)    Issue Date: 2/5/2025    Expiration Date: 4/6/2025    View NOV Form

Tanks Violation
1, 2 Miscellaneous - ATG is in alarm. T1 Gross Test Fail, T2 Leak Alarm, and T2 Gross Test Fail.
3 Miscellaneous - ATG shows T3 Diesel having 15 gallons .91" of water in it.
1 Overfill prevention equipment does not appear to function properly. - T1 premium overfill drop tube does not appear to function properly. The flapper valve is sticking in to the center of the tube. Repair shall be made and drop tube retested.
1, 2, 3 Precision tank test required.
1, 2, 3 Required monthly tank leak test records not available. - Multiple months do not have passing tank tests.
1, 2 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to the environment when the transfer hose is detached from the fill pipe (e.g., a spill catch basin). Spill containment equipment shall be maintained in a dry, clean state.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline - Premium Currently in use Federal $0.00
2 10000 Gasoline - Regular Currently in use Federal $0.00
3 10000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active

MFD Motorfuel Dispensing Forms

No Forms Found