Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2023158
Status: Active
Facility Name: Round Lake BP
Address: 320 Nippersink Road
Round Lake, IL 60073
County: Lake
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001203
Green Tag Issue Date: 1/12/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Stone Enterprises Round Lake, LLC
Owner Address: 320 Nippersink Road
Round Lake, IL 60073
Owner Status: Current Owner
Purchase Date: 8/17/2015
Type of Financial Responsibility: Letter of Credit
Financial Responsibility Reporting Due Date: 11/4/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/12/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037934 Stone Enterprises Round Lake, LLC Current Owner 8/17/2015
U0036765 Illini Petroleum, Inc. Former Owner 12/31/2012
U0027493 Amoco Oil Company Former Owner 1/1/1990
U0000552 BP Products North America, Inc. Former Owner 1/1/1990
U0023084 Graham Enterprise, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020251224 (Pending)    Issue Date: 5/8/2025    Expiration Date: 7/7/2025    View NOV Form

Tanks Violation
7 Annual electronic line leak detector test not completed. - Diesel tank FAILED ELLD testing (4/22/2025) "Diesel PLLd fails; there is too much air in the line for the leak detector to sense the leak. Further investigation needed."
5, 6, 7 Miscellaneous - Monthly line leak test records not available.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom.
5, 6, 7 Monthly impressed current log not available or maintained. - A log showing the rectifier gauge readings from Impressed Current rectifier shall be maintained monthly on site. Log shall show date; amp, volt, and hour meter readings; including the initials of the employee who recorded information.
5, 6, 7 Monthly impressed current system log not available or maintained. - A log showing the rectifier gauge readings from Impressed Current rectifier shall be maintained monthly on site. Log shall show date; amp, volt, and hour meter readings; including the initials of the employee who recorded information.
7 Open electrical conduit or junction boxes. - Open electric on Diesel STP.
5, 6, 7 Precision line test required. - Precision line test is required (Per 41 Ill Admin code 175.640(a)(4))
7 Precision line test required. - Precision line test is required due to suspected leak in diesel line. (Per 41 Ill Admin code 175.640(a)(4)(D))
5, 6, 7 Required monthly tank leak test records not available. - Maintain one NORMAL/PASS report per TANK, per month, from tank monitor.
5 Spill prevention equipment device is in disrepair and requires replacement. - Spill bucket lid is cracked and requires replacement.
5 Tank monitor does not appear to function properly and requires maintenance. - Tank monitor has no printer. Historic monthly tank and line leak test records have been provided using Titan remote printing. If records cannot be provided a printer will be required for future recordkeeping. (Per 41 Ill Admin code 175.630(c)(5)).
5 Tank monitor does not appear to function properly and requires maintenance. - Yellow and Green indicator lights are not functioning.
6 Tank monitor does not appear to function properly and requires maintenance. - Tank monitor has no printer. Historic monthly tank and line leak test records have been provided using Titan remote printing. If records cannot be provided a printer will be required for future recordkeeping. (Per 41 Ill Admin code 175.630(c)(5)).
6 Tank monitor does not appear to function properly and requires maintenance. - Yellow and Green indicator lights are not functioning.
7 Tank monitor does not appear to function properly and requires maintenance. - Tank monitor has no printer. Historic monthly tank and line leak test records have been provided using Titan remote printing. If records cannot be provided a printer will be required for future recordkeeping. (Per 41 Ill Admin code 175.630(c)(5)).
7 Tank monitor does not appear to function properly and requires maintenance. - Yellow and Green indicator lights are not functioning.
5, 6, 7 Tank precision test required. - Precision tank test is required due to missing or failed monthly monitoring (Per 41 Ill Admin code 175.630(c)(2))

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
90-1960 7/13/1990 Removal Log

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
90-1960 Eligible 9/17/1996 10/11/1996 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 500 Used Oil Removed Federal $0.00 07/01/1990 - REM
2 8000 Gasoline Removed Federal $0.00 07/01/1990 - REM
3 10000 Gasoline Removed Federal $0.00 07/01/1990 - REM
4 10000 Gasoline Removed Federal $0.00 07/01/1990 - REM
5 12000 Gasoline - Regular Currently in use Federal $0.00
6 12000 Gasoline - Premium Currently in use Federal $0.00
7 12000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found