Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2023142
Status: Active
Facility Name: Mogalma, LLC
Address: 389 East Irving Park Wood Dale, IL 60191
County: Du Page
Property Parcel: 03-15-209-039
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002413
Green Tag Issue Date: 2/21/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Mogalma, LLC
Owner Address: 389 E. Irving Park Rd. Wood Dale, IL 60191
Owner Status: Current Owner
Purchase Date: 10/31/2021
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 10/14/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 2/21/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040438 Mogalma, LLC Current Owner 10/31/2021
U0031108 TJV's Marathon Former Owner 12/14/2001
U0023834 BP Amoco Former Owner 4/14/1995
U0027493 Amoco Oil Company Former Owner 1/1/1988
U0000552 BP Products North America, Inc. Former Owner 1/1/1988

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252588 (Pending)    Issue Date: 10/1/2025    Expiration Date: 11/30/2025    View NOV Form

Tanks Violations
2, 3, 4 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Repair or replace STP sump lids or block parking lot area so no vehicles can enter the area.
Facility Financial responsibility must be reported yearly - Section 176.220 Proof of Financial Responsibility a) Proof of financial responsibility for Section 176.215(a), (b), (c), (d) or (e) shall be maintained on the respective OSFM forms, which may be complemented by industry customs and practices so long as the OSFM form language is utilized. The forms are available at https://sfm.illinois.gov/about/divisions/petroleumchemical- safety/applications-and-forms.html
4 Miscellaneous - Regular probe well stell cover is rusting away.
4 Miscellaneous - Regular vapor cap is broken.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30 day walk through is required to be performed and form kept on site for OSFM inspector.
2, 3, 4 Monthly impressed current log not available or maintained. - Monthly impressed current log is required to be completed and kept for OSFM inspector to review.
2, 3, 4 Monthly impressed current system log not available or maintained. - Monthly impressed current log is required to be completed and kept for OSFM inspector to review.
2, 3, 4 Tank monitor does not appear to function properly and requires maintenance. - The green and yellow indicator light is not working on the ATG. All lights need to be functioning.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
2023-0222 3/29/2023 Abandonment Log 00182-2023ABN

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
01-1569 Eligible 4/15/2005 5/19/2005 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 550 Petroleum Use: None
Product: Used Oil CERCLA Substance:
Status: Abandoned in place CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/29/1988 Abandoned Material: Inert material mixed with portland cement
Current Age: 37 Abandoned Date: 3/29/2023
Install Date: 12/18/1987 Red Tag Issue Date:
Last Used Date: 2/22/2022 Fee Due: $0.00
Product Date: 1/1/1988

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 3/21/2022 3/21/2023
Corrosion Prot - Tank Impressed Current Cathodic Protection 3/21/2022 3/21/2023
Leak Detect - Piping Gravity Feed N/A N/A
Leak Detect - Tank 110 - 600 gallons Manual Tank Gauging N/A N/A
Overfill Prev Device Less than 25 gallon fills N/A N/A
Piping Galvanized Steel Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/29/2021 6/29/2024
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/29/1988 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 12/18/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1988

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 8/13/2025 8/13/2026
Corrosion Prot - Tank Impressed Current Cathodic Protection 8/13/2025 8/13/2026
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/13/2025 8/13/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 8/13/2025 8/13/2026
Overfill Prev Device Overfill Drop Tube Valve 8/19/2024 8/19/2027
Piping Galvanized Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 8/19/2024 8/19/2027
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Galvanized Steel Single Wall Piping Precision Test (Piping) Pass 8/13/2025
Tank Steel Single Wall Precision Test (Tank) Pass 2/2/2023



Tank Number 3

Capacity: 10000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/29/1988 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 12/18/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1988

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 8/13/2025 8/13/2026
Corrosion Prot - Tank Impressed Current Cathodic Protection 8/13/2025 8/13/2026
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/13/2025 8/13/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 8/13/2025 8/13/2026
Overfill Prev Device Overfill Drop Tube Valve 8/19/2024 8/19/2027
Piping Galvanized Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 8/19/2024 8/19/2027
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Galvanized Steel Single Wall Piping Precision Test (Piping) Pass 8/13/2025
Tank Steel Single Wall Precision Test (Tank) Pass 2/2/2023



Tank Number 4

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/29/1988 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 12/18/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1988

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 8/13/2025 8/13/2026
Corrosion Prot - Tank Impressed Current Cathodic Protection 8/13/2025 8/13/2026
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/13/2025 8/13/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 8/13/2025 8/13/2026
Overfill Prev Device Overfill Drop Tube Valve 8/19/2024 8/19/2027
Piping Galvanized Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 8/19/2024 8/19/2027
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Galvanized Steel Single Wall Piping Precision Test (Piping) Pass 8/6/2025
Tank Steel Single Wall Precision Test (Tank) Pass 2/2/2023



Tank Number 5

Capacity: 1000 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 12/14/1987
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 12/14/1987
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 38 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 7

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 12/14/1987
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 27 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 8

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 12/14/1987
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A

MFD Motorfuel Dispensing Forms