Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0040167 |
Prism Motels, LLC |
Current Owner |
12/18/2018 |
| U0032493 |
Hashim, Mohammed |
Former Owner |
2/6/2004 |
| U0000552 |
BP Products North America, Inc. |
Former Owner |
12/31/1967 |
| U0029488 |
Mubarak, Ibrahim |
Former Owner |
|
| U0023834 |
BP Amoco |
Former Owner |
|
Permits (Unexpired)
Click for permit history
| Permit Number |
Type |
Status |
OSFM Receive Date |
Issue Date |
Expiration Date |
Documents |
| 00735-2026UPG |
Upgrade |
Approved / Issued |
6/25/2026 |
6/25/2026 |
12/26/2026 |
Documents |
Notice of Violations (Current)
NOV Number:
E0020253298
(Pending)
Issue Date:
12/18/2025
Expiration Date:
2/16/2026
View NOV Form
| Tanks |
Violations |
| 6 |
Drop tube valve or overfill alarm failed inspection. Repair or replace equipment. - Failed testing on 12-15-25 |
| 6 |
Spill prevention equipment device is in disrepair and requires replacement. - Cracked, failed testing on 12-15-25 |
IEMA Numbers Associated with the Facility
| IEMA Number |
Inspection Date |
Inspection Type |
Permit Number |
| 90-0323 |
3/4/1991 |
Removal Log |
|
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 90-0323 |
Eligible |
7/10/1996
|
7/25/1996
|
$10,000
|
|
Tank Number 1
| Capacity: |
500 |
|
Petroleum Use: |
|
| Product: |
Used Oil |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
3/1/1991 |
|
OSFM
First Notify Date: |
4/25/1986 |
|
Abandoned Material: |
|
| Current Age: |
33 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1958 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
1/1/1958 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
4000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
3/1/1991 |
|
OSFM
First Notify Date: |
4/25/1986 |
|
Abandoned Material: |
|
| Current Age: |
33 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1958 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
1/1/1958 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 3
| Capacity: |
4000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
3/1/1991 |
|
OSFM
First Notify Date: |
4/25/1986 |
|
Abandoned Material: |
|
| Current Age: |
33 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1958 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
1/1/1958 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 4
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
3/1/1991 |
|
OSFM
First Notify Date: |
4/25/1986 |
|
Abandoned Material: |
|
| Current Age: |
20 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1971 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
1/1/1971 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 5
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
5/29/2001 |
|
Abandoned Material: |
|
| Current Age: |
25 |
|
Abandoned Date: |
|
| Install Date: |
5/1/2001 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
5/1/2001 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Isolation Boots Flex Connector |
Not applicable |
Not applicable |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
12/15/2025 |
12/15/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 300 |
12/15/2025 |
12/15/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
12/15/2025 |
12/15/2028 |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
12/15/2025 |
12/15/2028 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
12/15/2025
|
Tank Number 6
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
5/29/2001 |
|
Abandoned Material: |
|
| Current Age: |
25 |
|
Abandoned Date: |
|
| Install Date: |
5/1/2001 |
|
Red Tag Issue Date: |
3/2/2026 |
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
5/1/2001 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Isolation Boots Flex Connector |
Not applicable |
Not applicable |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
12/15/2025 |
12/15/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 300 |
12/15/2025 |
12/15/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
7/18/2022 |
7/18/2025 |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
7/18/2022 |
7/18/2025 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
12/15/2025
|
Tank Number 7
| Capacity: |
5000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
5/29/2001 |
|
Abandoned Material: |
|
| Current Age: |
25 |
|
Abandoned Date: |
|
| Install Date: |
5/1/2001 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
5/1/2001 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Isolation Boots Flex Connector |
Not applicable |
Not applicable |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
12/15/2025 |
12/15/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 300 |
12/15/2025 |
12/15/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
12/15/2025 |
12/15/2028 |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
1/24/2025 |
1/24/2028 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
12/15/2025 |
12/15/2028 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
12/15/2025
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 5/6
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found