Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2023098
Status: Active
Facility Name: Hala Dolton d/b/a Exxon
Address: 1421 E. Sibley Blvd.
Dolton, IL 60419
County: Cook
Property Parcel: 29-11-401-016-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000229
Green Tag Issue Date: 1/25/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: M & Y Dolton Property, LLC
Owner Address: 1421 E. Sibley Blvd.
Dolton, IL 60419
Owner Status: Current Owner
Purchase Date: 11/22/2019
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 3/13/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/25/2024 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039821 M & Y Dolton Property, LLC Current Owner 11/22/2019
U0033575 153 Broadway, Inc. Former Owner 6/20/2006
U0023834 BP Amoco Former Owner 4/3/1995
U0027493 Amoco Oil Company Former Owner 1/1/1981
U0000552 BP Products North America, Inc. Former Owner 1/1/1981

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250245 (Pending)    Issue Date: 1/30/2025    Expiration Date: 3/31/2025    View NOV Form

Tanks Violation
Facility Facility Operation and Maintenance Plan not completed or available. - Not filled out completely.
Facility Financial responsibility must be reported yearly - Financial Responsibility form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility.
1, 2, 3 Line interstitial sensors have been raised and rendered inoperational. - (Dispensers. 5/6 and 7/8)
1, 2, 3 Line leak detection equipment in alarm or failed test, must repair or replace. - L5 (Dispenser 9/10) sensor in alarm. Repair/replace to clear alarm.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at https://sfm.illinois.gov.
Facility Missing copy of emergency instructions or emergency procedures plan - Form can be found at https://sfm.illinois.gov to download and complete.
1, 2, 3 Monthly line interstitial sensor records not available. - Maintain one NORMAL report per LINE, per month, from ATG. (Liquid Status)
1, 3 Open electrical conduit or junction boxes. - Broken conduit in Stps. Repair/replace. (Regular East and Premium)
1, 2, 3 Piping interstitial must be open in all sumps - (Stps and dispenser sumps)
3 Precision line test required. - Presicion test on Premium line due to gas found in interstitial of piping. Premium line will be shut down until test is completed and sumbitted to OSFM.
1, 2, 3 Required monthly tank leak test records not available. - Maintain one PASSING report per TANK, per month, from ATG. Reference 175.630 c)2)B) (CSLD)
1, 2, 3 Tank internal lining inspection past due (Required every 5 years). - 5-year lining inspection is overdue. Internal lining inspection shall be conducted by an OSFM licensed lining contractor. Original notification form dated 4/25/1996 indicates the tanks are single wall fiberglass, with lined interior. An upgrade log dated 6/4/1993 verifying the work for upgrade permit 6529-1992UPG was sent in, which also indicated that the tanks were lined, single Wall fiberglass tanks.
1, 2, 3 Tank precision test required. - Due to missing monthly tapes.
1, 2, 3 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Remove Liquid in dispenser 9/10.

NOV Number: E0020250246 (Pending)    Issue Date: 1/30/2025    Expiration Date: 3/31/2025    View NOV Form

Tanks Violation
Facility Code complying instruction/warning signs are not properly mounted at each dispenser island - Minimum signage is not up to code. Reference 175.210 o)
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h)

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline - Regular Currently in use Federal $0.00
2 10000 Gasoline - Regular Currently in use Federal $0.00
3 10000 Gasoline - Premium Currently in use Federal $0.00
4 1000 Gasoline Removed Exempt 09/24/1999 - REM

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active

MFD Motorfuel Dispensing Forms

No Forms Found