Facility |
Facility Operation and Maintenance Plan not completed or available. - Not filled out completely. |
Facility |
Financial responsibility must be reported yearly - Financial Responsibility form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility. |
1, 2, 3 |
Line interstitial sensors have been raised and rendered inoperational. - (Dispensers. 5/6 and 7/8) |
1, 2, 3 |
Line leak detection equipment in alarm or failed test, must repair or replace. - L5 (Dispenser 9/10) sensor in alarm. Repair/replace to clear alarm. |
Facility |
Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at https://sfm.illinois.gov. |
Facility |
Missing copy of emergency instructions or emergency procedures plan - Form can be found at https://sfm.illinois.gov to download and complete. |
1, 2, 3 |
Monthly line interstitial sensor records not available. - Maintain one NORMAL report per LINE, per month, from ATG. (Liquid Status) |
1, 3 |
Open electrical conduit or junction boxes. - Broken conduit in Stps. Repair/replace. (Regular East and Premium) |
1, 2, 3 |
Piping interstitial must be open in all sumps - (Stps and dispenser sumps) |
3 |
Precision line test required. - Presicion test on Premium line due to gas found in interstitial of piping. Premium line will be shut down until test is completed and sumbitted to OSFM. |
1, 2, 3 |
Required monthly tank leak test records not available. - Maintain one PASSING report per TANK, per month, from ATG. Reference 175.630 c)2)B) (CSLD) |
1, 2, 3 |
Tank internal lining inspection past due (Required every 5 years). - 5-year lining inspection is overdue. Internal lining inspection shall be conducted by an OSFM licensed lining contractor. Original notification form dated 4/25/1996 indicates the tanks are single wall fiberglass, with lined interior. An upgrade log dated 6/4/1993 verifying the work for upgrade permit 6529-1992UPG was sent in, which also indicated that the tanks were lined, single Wall fiberglass tanks. |
1, 2, 3 |
Tank precision test required. - Due to missing monthly tapes. |
1, 2, 3 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Remove Liquid in dispenser 9/10. |