Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2023093
Status: Active
Facility Name: Fuller's Gas & Quick Lube
Address: 5620 South Brainard Avenue Countryside, IL 60525
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000601
Green Tag Issue Date: 12/4/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Walter Fuller
Owner Address:
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 11/19/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0032586 Fuller, Walter Current Owner
U0000552 BP Products North America, Inc. Former Owner 5/19/1994
U0023834 BP Amoco Former Owner 6/13/1969
U0000565 Amoco Oil Co Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020261069 (Pending)    Issue Date: 4/21/2026    Expiration Date: 6/20/2026    View NOV Form

Tanks Violations
8, 9 Annual electronic line leak detector test not completed.
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
7, 8, 9 Annual leak detection certification not completed (Required annually).
Facility Facility Operation and Maintenance Plan not completed or available.
7, 8, 9 Line interstitial sensor functional test not accomplished (Required annually).
Facility Missing copies of 30 day Walkthrough Inspection Report.
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copies of current testing certificates for operator training
Facility Missing copy of emergency instructions or emergency procedures plan
Facility Missing list of designated Class A/B & C Operators
7, 8, 9 Monthly line interstitial sensor records not available. - PLEASE LOCATE THE LAST 2 YEARS
7, 8, 9 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - LAST TESTED ON 6-30-22
7, 8, 9 Required monthly tank interstitial sensor records not available. - PLEASE LOCATE THE LAST 2 YEARS OR TIGHTNESS TEST TANKS
7, 8, 9 Required monthly tank leak test records not available. - PLEASE SUBMIT THE LAST 2 YEARS OR TIGHTNESS TEST TANKS
7, 8, 9 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
7, 8, 9 Tank interstitial sensor functional test not accomplished (Required annually).

NOV Number: E0020261070 (Pending)    Issue Date: 4/21/2026    Expiration Date: 6/20/2026    View NOV Form

Tanks Violations
Facility Code complying instruction/warning signs are not properly mounted at each dispenser island - PLEASE REPLACE FADED SIGNS

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
89-0545 Eligible 5/27/1994 6/14/1994 $50,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 550 Used Oil Removed Federal $0.00 06/23/1989 - REM
2 6000 Gasoline Removed Federal $0.00 03/30/1993 - REM
3 6000 Gasoline Removed Federal $0.00 03/30/1993 - REM
4 8000 Gasoline Removed Federal $0.00 03/30/1993 - REM
5 10000 Gasoline Removed Federal $0.00 03/30/1993 - REM
6 550 Used Oil Removed Federal $0.00 03/30/1993 - REM
7 12000 Gasoline - Regular Currently in use Federal $0.00
8 7000 Gasoline - Premium Currently in use Federal $0.00
9 5000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found