Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2022960
Status: Active
Facility Name: Montrose BP
Address: 3201 W. Montrose Avenue
Chicago, IL 60618
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000495
Green Tag Issue Date: 8/25/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: 3201 Montrose Real Estate, Inc.
Owner Address: 3201 W. Montrose St.
Chicago, IL 60618
Owner Status: Current Owner
Purchase Date: 3/30/2012
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 2/21/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/22/2021 12/31/2023

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0036059 3201 Montrose Real Estate, Inc. Current Owner 3/30/2012
U0035268 Sasafrasnet Beep-Beep, LLC Former Owner 3/31/2009
U0023834 BP Amoco Former Owner 4/8/1995
U0027493 Amoco Oil Company Former Owner 1/1/1987
U0000552 BP Products North America, Inc. Former Owner 1/1/1987

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250446 (Pending)    Issue Date: 2/21/2025    Expiration Date: 4/22/2025    View NOV Form

Tanks Violation
2 Line leak detection equipment in alarm or failed test, must repair or replace. - Veeder Root shows WPLLD Shutdown alarm for (Veeder Root numbered PLD #2) OSFM Tank #1 is Premium with MLD. OSFM Tank # 2 10K Regular has a WPLLD installed and tested by Protanic . OSFM Tank #3 12K Regular has a WPPLD installed and tested. Either OSFM tank #2 10K is manifolded and has a check valve requiring changes to OSFM database and programming on Veeder Root to get rid of the PLD #2 alarm and Line Shutdown.. or The WPLLD is not functioning correctly and needs a MLD installed and WPPLD programing removed for the Line.
2 Precision line test required. - If the regular tanks are not manifolded then OSFM tank #2 has not been monitored and will need to have line tested as no leak detection has been maintained on that set of lines.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
05-0768 Eligible 3/18/2009 4/7/2009 $10,000
09-0870 Eligible 2/8/2010 3/3/2010 $10,000
05-0768 Eligible 3/3/2010 4/22/2010 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/22/1987 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 9/1/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 7/12/2024 7/12/2025
Corrosion Prot - Tank Impressed Current Cathodic Protection 7/12/2024 7/12/2025
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/12/2024 7/12/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R with CSLD 7/12/2024 7/12/2025
Overfill Prev Device Overfill Drop Tube Valve 7/30/2024 7/30/2027
Piping Steel Single Wall Piping N/A N/A
Spill Contain Device Double Wall Spill Bucket 7/30/2024 7/30/2027
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Steel Single Wall Piping Precision Test (Piping) Pass 7/12/2024
Tank Steel Single Wall Precision Test (Tank) Pass 5/3/2019



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/22/1987 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 9/1/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 7/12/2024 7/12/2025
Corrosion Prot - Tank Impressed Current Cathodic Protection 7/12/2024 7/12/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 7/12/2024 7/12/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R with CSLD 7/12/2024 7/12/2025
Overfill Prev Device Overfill Drop Tube Valve 7/30/2024 7/30/2027
Piping Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 7/12/2024 7/12/2027
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/22/1987 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 9/1/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 7/12/2024 7/12/2025
Corrosion Prot - Tank Impressed Current Cathodic Protection 7/12/2024 7/12/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 7/12/2024 7/12/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R with CSLD 7/12/2024 7/12/2025
Overfill Prev Device Overfill Drop Tube Valve 7/12/2024 7/12/2027
Piping Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 7/12/2024 7/12/2027
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 500 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 9/9/1987
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 2 Abandoned Date:
Install Date: 4/1/1985 Red Tag Issue Date:
Last Used Date: 1/1/1987 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 9/9/1987
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 4/1/1967 Red Tag Issue Date:
Last Used Date: 1/1/1987 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 9/9/1987
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 4/1/1967 Red Tag Issue Date:
Last Used Date: 1/1/1987 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 7

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 9/9/1987
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 17 Abandoned Date:
Install Date: 4/1/1970 Red Tag Issue Date:
Last Used Date: 1/1/1987 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found