Notice of Violations (Current)
NOV Number:
E0020261909
(Pending)
Issue Date:
7/28/2026
Expiration Date:
9/26/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h) |
NOV Number:
E0020261910
(Pending)
Issue Date:
7/28/2026
Expiration Date:
9/26/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. - Only one out of 2 emergency stops were tested. Need to test all of them yearly. |
| 3, 4 |
Annual tank impressed current system appears not to be operational. - Green light on rectifier is not working. Repair/Replace. |
| 3, 4 |
Tank monitor does not appear to function properly and requires maintenance. - Indicator light(s) on panel of Veeder-Root ATG is/are not functional. Replace as necessary to provide proper operation. (Green and Yellow light out) All lights need to be working. |