Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2021207
Status: Active
Facility Name: Circle K #6744
Address: 6050 W. Grand Ave.
Gurnee, IL 60031
County: Lake
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: AA00837
Green Tag Issue Date: 2/10/2025
Green Tag Expiration Date: 12/31/2027

Owner Details

Owner Name: RDK Ventures, LLC
Owner Address: 1120 W. Warner Rd.
Tempe, AZ 85284
Owner Status: Current Owner
Purchase Date: 1/7/2010
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/24/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 2/10/2025 12/31/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures, LLC Current Owner 1/7/2010
U0013849 Shell Oil Products Former Owner 12/31/1967
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner
U0027449 Equilon Enterprises, LLC Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

No Notice of Violations Found

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
90-1541 3/17/1992 Removal Log

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
90-2167 Eligible 3/28/1994 4/4/1994 $10,000
08-1210 Eligible 10/1/2008 11/21/2008 $10,000
20190586 Eligible 7/29/2019 8/1/2019 $5,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/17/1992
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 1/1/1976 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/17/1992
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 1/1/1976 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/17/1992
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 1/1/1976 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/18/1992 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 4/15/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/16/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Other Non-vented check valve N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/25/2025 3/25/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 3/25/2025 3/25/2026
Overfill Prev Device Overfill Drop Tube Valve 6/6/2024 6/6/2027
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 5/23/2024 5/23/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/25/2025 3/25/2026
Spill Contain Device Double Wall Spill Bucket 4/25/2024 4/25/2027
Tank Fiberglass Double Wall Owens Corning Brine Filled N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 3/25/2025



Tank Number 5

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/18/1992 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 4/15/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/16/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/25/2025 3/25/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/25/2025 3/25/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 3/25/2025 3/25/2026
Overfill Prev Device Overfill Drop Tube Valve 6/6/2024 6/6/2027
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 5/23/2024 5/23/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/25/2025 3/25/2026
Spill Contain Device Single Wall Spill Bucket 4/25/2024 4/25/2027
Tank Fiberglass Double Wall Owens Corning Brine Filled N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 3/25/2025



Tank Number 6

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/18/1992 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 4/15/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/16/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/25/2025 3/25/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/25/2025 3/25/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 3/25/2025 3/25/2026
Overfill Prev Device Overfill Drop Tube Valve 4/25/2024 4/25/2027
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 5/23/2024 5/23/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/25/2025 3/25/2026
Spill Contain Device Single Wall Spill Bucket 4/25/2024 4/25/2027
Tank Fiberglass Double Wall Owens Corning Brine Filled N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 3/25/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/23/2024 5/23/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/25/2025 3/25/2026



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/23/2024 5/23/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/25/2025 3/25/2026



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/23/2024 5/23/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/25/2025 3/25/2026



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/23/2024 5/23/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/25/2025 3/25/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/23/2024 5/23/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/25/2025 3/25/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/23/2024 5/23/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/25/2025 3/25/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/23/2024 5/23/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/25/2025 3/25/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/23/2024 5/23/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/25/2025 3/25/2026

MFD Motorfuel Dispensing Forms

No Forms Found