Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2021197
Status: Active
Facility Name: Lake Forest Shell
Address: 193 E. Deerpath Rd.
Lake Forest, IL 60045
County: Lake
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001234
Green Tag Issue Date: 4/3/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: BGL Properties, LLC
Owner Address: 193 E. Deerpath Rd.
Lake Forest, IL 60045
Owner Status: Current Owner
Purchase Date: 5/16/2018
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 8/24/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 4/3/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039212 BGL Properties, LLC Current Owner 5/16/2018
U0035735 True North Energy, LLC Former Owner 3/8/2010
U0013849 Shell Oil Products Former Owner 3/13/1992
U0027449 Equilon Enterprises, LLC Former Owner 2/1/1986
U0000926 Atlantic Richfield Co Former Owner 12/31/1967
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250511 (Pending)    Issue Date: 2/27/2025    Expiration Date: 4/28/2025    View NOV Form

Tanks Violation
3 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Overfill drop tube failed.
1, 2, 3 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - STP and UDC Sumps require testing.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
03-0451 Eligible 6/4/2003 7/7/2003 $10,000
08-0907 Eligible 10/1/2008 11/20/2008 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 45 Abandoned Date:
Install Date: 11/1/1979 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/1/1979

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Other Non-vented check valve N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R with CSLD 1/21/2025 1/21/2026
Overfill Prev Device Overfill Drop Tube Valve 1/21/2025 1/21/2028
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 11/23/2021 11/23/2024
Leak Detect - Piping Stand Alone Sump Sensor Non-Discriminating 12/11/2019 12/11/2020
Leak Detect - Piping Sump Sensor 1/21/2025 1/21/2026
Spill Contain Device Single Wall Spill Bucket 1/21/2025 1/21/2028
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 3/12/2009



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 42 Abandoned Date:
Install Date: 11/5/1982 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/5/1982

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/21/2025 1/21/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R with CSLD 1/21/2025 1/21/2026
Overfill Prev Device Overfill Drop Tube Valve 1/21/2025 1/21/2028
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 11/23/2021 11/23/2024
Leak Detect - Piping Stand Alone Sump Sensor Non-Discriminating 12/11/2019 12/11/2020
Leak Detect - Piping Sump Sensor 1/21/2025 1/21/2026
Spill Contain Device Single Wall Spill Bucket 1/21/2025 1/21/2028
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 3/12/2009



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 42 Abandoned Date:
Install Date: 11/5/1982 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/5/1982

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/21/2025 1/21/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R with CSLD 1/21/2025 1/21/2026
Overfill Prev Device Overfill Drop Tube Valve 11/23/2021 11/23/2024
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 11/23/2021 11/23/2024
Leak Detect - Piping Stand Alone Sump Sensor Non-Discriminating 12/11/2019 12/11/2020
Leak Detect - Piping Sump Sensor 1/21/2025 1/21/2026
Spill Contain Device Single Wall Spill Bucket 1/21/2025 1/21/2028
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 3/12/2009



Tank Number 4

Capacity: 550 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 4/28/1989
OSFM First Notify Date: 4/28/1986 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 1/1/1976 Red Tag Issue Date:
Last Used Date: 6/1/1977 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 1000 Petroleum Use:
Product: Fuel Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: State Removed Date: 4/28/1989
OSFM First Notify Date: 10/23/1991 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 1/1/1976 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/3

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 11/23/2021 11/23/2024
Leak Detect - Piping Stand Alone Sump Sensor 1/21/2025 1/21/2026



Name\ID 2/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 11/23/2021 11/23/2024
Leak Detect - Piping Stand Alone Sump Sensor 1/21/2025 1/21/2026



Name\ID 5/7

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 11/23/2021 11/23/2024
Leak Detect - Piping Stand Alone Sump Sensor 1/21/2025 1/21/2026



Name\ID 6/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 11/23/2021 11/23/2024
Leak Detect - Piping Stand Alone Sump Sensor 1/21/2025 1/21/2026

MFD Motorfuel Dispensing Forms

No Forms Found