7 |
Annual electronic line leak detector test not completed. - Annual leak detection certification (leak detectors) not completed. Testing shall be performed. |
7 |
Drop tube valve or overfill alarm failed inspection. Repair or replace equipment. - Triennial inspection/testing of overfill device (drop tube valve ) failed 3/4/2025. Repair/replace as necessary; device shall be re-inspected with passing results and uploaded to OSFM website. |
7 |
Failed to Empty the Tank to 1" or Less |
7 |
Submit Notification Form For Tank Status Change - Submit OSFM Notification Form placing all tanks in Temporarily Out of Use status.
The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of a tank status change. According to the previous facility manager this tank has been out of service since at least May of 2024 and it received its last fuel delivery on 2/27/2024, per records. |
6, 7, 8 |
Tank monitor does not appear to function properly and requires maintenance. - Indicator lightS (Green and Yellow) on panel of Veeder-Root ATG are not functional. Replace as necessary to provide proper operation. |