1, 2, 3 |
Dispensers - hoses cracked, split or worn and require replacement - Replace main hose. |
3 |
Line interstitial sensors have been raised and rendered inoperational. - Premium STP sump has a raised sensor. 175.640 a) 2) All new and existing sump sensors must be installed so as to detect liquid per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump. |
2 |
Miscellaneous - Replace vapor cap. |
2 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to
the environment when the transfer hose is detached from the fill
pipe (e.g., a spill catch basin). Spill containment equipment shall
be maintained in a dry, clean state. |
1 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Tank 1 STP sump triannual testing is required. Passing results shall be entered on the OSFM portal. |
3 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Remove liquid from premium STP sump. |