Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2021173
Status: Active
Facility Name: Shell Carol Stream
Address: 106 W. North Ave.
Carol Stream, IL 60188
County: Du Page
Property Parcel: 02-32-401-009
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003367
Green Tag Issue Date: 12/12/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Yogeshwari, Inc.
Owner Address: 3219 Tall Grass Drive
Naperville, IL 60564
Owner Status: Current Owner
Purchase Date: 10/19/2022
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 11/9/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 12/12/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040924 Yogeshwari, Inc. Current Owner 10/19/2022
U0037012 106 North, LLC Former Owner 6/12/2012
U0035671 RDK Ventures, LLC Former Owner 1/7/2010
U0013849 Shell Oil Products Former Owner 12/31/1967
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner
U0027449 Equilon Enterprises, LLC Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020251062 (Pending)    Issue Date: 4/18/2025    Expiration Date: 6/17/2025    View NOV Form

Tanks Violation
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom.

NOV Number: E0020251063 (Pending)    Issue Date: 4/18/2025    Expiration Date: 6/17/2025    View NOV Form

Tanks Violation
1, 2, 3 Dispensers - hoses cracked, split or worn and require replacement - Replace main hose.
3 Line interstitial sensors have been raised and rendered inoperational. - Premium STP sump has a raised sensor. 175.640 a) 2) All new and existing sump sensors must be installed so as to detect liquid per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump.
2 Miscellaneous - Replace vapor cap.
2 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to the environment when the transfer hose is detached from the fill pipe (e.g., a spill catch basin). Spill containment equipment shall be maintained in a dry, clean state.
1 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Tank 1 STP sump triannual testing is required. Passing results shall be entered on the OSFM portal.
3 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Remove liquid from premium STP sump.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
08-1055 Eligible 10/1/2008 11/18/2008 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline - Regular Currently in use Federal $0.00
2 10000 Gasoline - Regular Currently in use Federal $0.00
3 8000 Gasoline - Premium Currently in use Federal $0.00
4 1000 Used Oil Removed Federal $0.00 05/27/1998 - REM

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found