Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shut off switch needs annual testing performed. OSFM form shall be kept on site. |
4, 5 |
Dispensers - hoses cracked, split or worn and require replacement - Replace main hose. |
4, 5 |
Document that emergency shut-off (shear valves) are in proper working order - Shear valves need annual testing performed. OSFM form shall be completed and kept on site. |
Facility |
Facility Operation and Maintenance Plan not completed or available. - Operations and maintenance template needs to be updated and kept on site. |
Facility |
Missing copies of Annual Walkthrough Inspection Report. - Annual walkthrough needs to be performed. OSFM form shall be completed and kept on site. |
Facility |
Missing copy of emergency instructions or emergency procedures plan - Emergency procedures plan needs to be updated and kept on site. |
4, 5 |
Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps. |
4, 5 |
Tank monitor does not appear to function properly and requires maintenance. - Green light is out and needs to be replaced. The yellow lense cap is missing and needs to be replaced. |