Deficiencies (Current)
NOV Number:
E0020241087
(Pending)
Issue Date:
4/11/2024
Expiration Date:
6/10/2024
View NOV Form
Tanks |
Deficiency |
1, 2, 3 |
Line interstitial sensors have been raised and rendered inoperational. - Sensors must be placed per manufactures recommendation or at the bottom of the sump.
All dispensers. |
1, 2, 3 |
Monthly line interstitial sensor records not available. |
1, 2, 3 |
Precision line test required. |
1, 2, 3 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Pill buckets must be clean and dry. |