5, 6, 7 |
Dispensers - hoses cracked, split or worn and require replacement - The main hose has cracks in it and needs to be replacxed. The dispenser hose should not be used until it is replaced. |
Facility |
Facility Operation and Maintenance Plan not completed or available. |
Facility |
Miscellaneous - Emergency shut off switch at control station needs a sign.
175.210 d) 3) Equipped with an emergency stop at all control stations, which shall be
conspicuously marked and readily accessible to the attendant, whether or
not the control station is less than 20 feet from any dispenser or a security
booth is provided for the attendant. The emergency stop shall be located
in a position to allow all dispensing devices to be readily visible to the
attendant, or as approved by OSFM. Each emergency stop shall be
identified by a sign on all-weather materials stating "EMERGENCY
STOP" in 2 inch red capital letters. |
Facility |
Miscellaneous - There is a slight leak from pipe under dispenser 3/4. Repair leak and clean the bottom of the sump. |
Facility |
Missing copy of emergency instructions or emergency procedures plan |
5, 6 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Spill and vapor buckets have liquid in them. The bottom of the multi port sump has water in it and should be removed prior to activating sensor. |