Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2021129
Status: Active
Facility Name: Circle K #6790
Address: 7201 W. North Avenue River Forest, IL 60305
County: Cook
Property Parcel: 15-01-205-057-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000313
Green Tag Issue Date: 3/18/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: RDK Ventures, LLC
Owner Address: 1120 W. Warner Rd. Tempe, AZ 85284
Owner Status: Current Owner
Purchase Date: 1/7/2010
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 1/26/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/18/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures, LLC Current Owner 1/7/2010
U0013849 Shell Oil Products Former Owner 12/31/1967
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner
U0027449 Equilon Enterprises, LLC Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

No Notice of Violations Found

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
08-1144 Eligible 10/1/2008 11/14/2008 $15,000
20181124 Eligible 1/28/2019 2/1/2019 $5,000 Letter
20210017 Eligible 2/16/2021 2/16/2021 $5,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 9 Abandoned Date:
Install Date: 6/23/2016 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 5/28/2025 5/28/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/28/2025 5/28/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/28/2025 5/28/2026
Overfill Prev Device Overfill Drop Tube Valve 9/17/2024 9/17/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 5/22/2024 5/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 5/28/2025 5/28/2026
Spill Contain Device Double Wall Spill Bucket 9/17/2024 9/17/2027
Tank Stand Alone System N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 5/28/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 5/28/2025



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 9 Abandoned Date:
Install Date: 6/23/2016 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 5/28/2025 5/28/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/28/2025 5/28/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/28/2025 5/28/2026
Overfill Prev Device Overfill Drop Tube Valve 6/4/2024 6/4/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 5/22/2024 5/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 5/28/2025 5/28/2026
Spill Contain Device Double Wall Spill Bucket 6/4/2024 6/4/2027
Tank Stand Alone System N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 5/28/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 5/28/2025



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 9 Abandoned Date:
Install Date: 7/6/2016 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/28/2025 5/28/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/28/2025 5/28/2026
Overfill Prev Device Overfill Drop Tube Valve 6/4/2024 6/4/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 5/22/2024 5/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 5/28/2025 5/28/2026
Spill Contain Device Single Wall Spill Bucket 6/4/2024 6/4/2027
Tank Stand Alone System N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 9/27/2022
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 5/28/2025



Tank Number 4

Capacity: 1000 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/1/1990
OSFM First Notify Date: 8/6/1990 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 1000 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/1/1990
OSFM First Notify Date: 8/6/1990 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 1000 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/1/1990
OSFM First Notify Date: 8/6/1990 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 7

Capacity: 550 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/1/1990
OSFM First Notify Date: 8/6/1990 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/22/2024 5/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 5/28/2025 5/28/2026



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/22/2024 5/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 5/28/2025 5/28/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/22/2024 5/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 5/28/2025 5/28/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/22/2024 5/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 5/28/2025 5/28/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/22/2024 5/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 5/28/2025 5/28/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/22/2024 5/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 5/28/2025 5/28/2026

MFD Motorfuel Dispensing Forms

No Forms Found