Notice of Violatlions (Current)
NOV Number:
E0020260787
(Pending)
Issue Date:
3/25/2026
Expiration Date:
5/24/2026
View NOV Form
| Tanks |
Violations |
| 6 |
Miscellaneous - Any UST that fails to meet the criteria and requirements of Subparts D, E and F
shall be removed within 60 days after receipt of a Notice of Violation requiring its
removal. 175.400 d)
Remove By: 5/16/2026 Date Last Used: 3/19/2026
The leaking tank does not meet the criteria and requirements of Subparts D, E and F. |
| 6 |
Submit Notification Form For Tank Status Change - Submit Notification form placing tank out of service.
The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This
(NovUST 09/21/2025) Page 1 of 2
form is required to be submitted within 30 days of a tank status change.
Remarks: |
NOV Number:
E0020261043
(Pending)
Issue Date:
4/21/2026
Expiration Date:
6/20/2026
View NOV Form
| Tanks |
Violations |
| 7, 8 |
Annual electronic line leak detector test not completed. - Line leak detectors need annual testing. Testing shall be performed and passing results entered on OSFM portal. |
| 7, 8 |
Annual leak detection certification not completed (Required annually). |
| 7, 8 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). |
| 7, 8 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - STP's and UDC's |