Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0041092 |
Standard Bank & Trust Co. Trust number 19482 |
Current Owner |
7/3/2006 |
| U0031131 |
Assaf, Suhail |
Former Owner |
|
| U0013849 |
Shell Oil Products |
Former Owner |
|
Notice of Violations (Current)
No Notice of Violations Found
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 92-0080 |
Eligible |
4/24/2002
|
5/28/2002
|
$10,000
|
|
Tank Number 1
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
6/22/1992 |
|
OSFM
First Notify Date: |
4/23/1986 |
|
Abandoned Material: |
|
| Current Age: |
22 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1970 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/1/1992 |
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1970 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
6/22/1992 |
|
OSFM
First Notify Date: |
4/23/1986 |
|
Abandoned Material: |
|
| Current Age: |
22 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1970 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/1/1992 |
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1970 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 3
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
6/22/1992 |
|
OSFM
First Notify Date: |
4/23/1986 |
|
Abandoned Material: |
|
| Current Age: |
22 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1970 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/1/1992 |
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1970 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 4
| Capacity: |
550 |
|
Petroleum Use: |
|
| Product: |
Used Oil |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
6/22/1992 |
|
OSFM
First Notify Date: |
4/23/1986 |
|
Abandoned Material: |
|
| Current Age: |
22 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1970 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/1/1992 |
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1970 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 5
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
4/10/2009 |
|
Abandoned Material: |
|
| Current Age: |
23 |
|
Abandoned Date: |
|
| Install Date: |
3/7/2003 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
3/7/2003 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
9/8/2025 |
9/8/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
9/8/2025 |
9/8/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
8/28/2023 |
8/28/2026 |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
8/28/2023 |
8/28/2026 |
Leak Detect - Piping
|
Sump Sensor |
8/28/2023 |
8/28/2026 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
8/28/2023 |
8/28/2026 |
|
Tank
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall
|
Precision Test (Piping)
|
Pass
|
9/8/2025
|
|
Tank
|
Fiberglass Double Wall
|
Precision Test (Tank)
|
Pass
|
4/4/2019
|
Tank Number 6
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
4/10/2009 |
|
Abandoned Material: |
|
| Current Age: |
23 |
|
Abandoned Date: |
|
| Install Date: |
3/7/2003 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
3/7/2003 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
9/8/2025 |
9/8/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
9/8/2025 |
9/8/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
8/28/2023 |
8/28/2026 |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
8/28/2023 |
8/28/2026 |
Leak Detect - Piping
|
Sump Sensor |
8/28/2023 |
8/28/2026 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
8/28/2023 |
8/28/2026 |
|
Tank
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall
|
Precision Test (Piping)
|
Pass
|
9/8/2025
|
|
Tank
|
Fiberglass Double Wall
|
Precision Test (Tank)
|
Pass
|
4/4/2019
|
Tank Number 7
| Capacity: |
4000 |
|
Petroleum Use: |
|
| Product: |
E85 |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
4/10/2009 |
|
Abandoned Material: |
|
| Current Age: |
23 |
|
Abandoned Date: |
|
| Install Date: |
3/7/2003 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
3/7/2003 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
9/8/2025 |
9/8/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
9/8/2025 |
9/8/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
1/11/2024 |
1/11/2027 |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
8/28/2023 |
8/28/2026 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
8/28/2023 |
8/28/2026 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
8/28/2023 |
8/28/2026 |
|
Tank
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall
|
Precision Test (Piping)
|
Pass
|
9/8/2025
|
|
Tank
|
Fiberglass Double Wall
|
Precision Test (Tank)
|
Pass
|
4/4/2019
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
8/28/2023
|
8/28/2026
|
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
9/8/2025
|
9/8/2026
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
8/28/2023
|
8/28/2026
|
Leak Detect - Piping
|
Sump Sensor |
9/8/2025
|
9/8/2026
|
Name\ID 5/6
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
8/28/2023
|
8/28/2026
|
Leak Detect - Piping
|
Sump Sensor |
9/8/2025
|
9/8/2026
|
Name\ID 7/8
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
8/28/2023
|
8/28/2026
|
Leak Detect - Piping
|
Sump Sensor |
9/8/2025
|
9/8/2026
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found