Notice of Violations (Current)
NOV Number:
E0020261786
(Pending)
Issue Date:
7/14/2026
Expiration Date:
9/12/2026
View NOV Form
| Tanks |
Violations |
| 2, 3 |
Submit Notification Form For Tank Status Change - The Notification Form is available at: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of a tank status change.
Per 175.810(a)(1), when placing tanks out of service, the tank and lines must be emptied
immediately. The UST is considered empty when all materials have been removed to one inch or less. It
appears that there is still product in both tanks (2 & 3). Product must be removed
immediately! |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
600 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
4/30/1997 |
|
OSFM
First Notify Date: |
5/2/1986 |
|
Abandoned Material: |
|
| Current Age: |
32 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
4/1/1997 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
2500 |
|
Petroleum Use: |
Dispensing |
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Out of service |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
4/28/1998 |
|
Abandoned Material: |
|
| Current Age: |
29 |
|
Abandoned Date: |
|
| Install Date: |
3/14/1997 |
|
Red Tag Issue Date: |
7/14/2026 |
| Last Used Date: |
7/14/2026 |
|
Fee Due: |
$0.00 |
| Product Date: |
3/25/1997 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Composite Secondary Containment |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
5/11/2026 |
5/11/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 |
5/11/2026 |
5/11/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
5/11/2026 |
5/11/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
5/13/2024 |
5/13/2027 |
|
Piping
|
Fiberglass Chase |
Not applicable |
Not applicable |
|
Piping
|
Steel Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
5/24/2024 |
5/26/2026 |
Leak Detect - Piping
|
Sump Sensor |
5/24/2024 |
5/26/2026 |
|
Spill Contain Device
|
Manhole Field Constructed |
5/26/2026 |
5/26/2029 |
|
Tank
|
Fiberglass Brine Filled Double Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Chase
|
Precision Test (Piping)
|
Pass
|
5/11/2026
|
|
Piping
|
Fiberglass Secondary Containment steel primary
|
Precision Test (Piping)
|
Pass
|
5/8/2020
|
|
Piping
|
Steel Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
3/24/2022
|
|
Tank
|
Fiberglass Brine Filled Double Wall
|
Precision Test (Tank)
|
Pass
|
8/11/2022
|
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors
|
Sensor Functional
|
Pass
|
7/30/2010
|
|
Leak Detect - Piping
|
Sump Sensor
|
Sensor Functional
|
Pass
|
7/30/2010
|
Tank Number 3
| Capacity: |
4000 |
|
Petroleum Use: |
Dispensing |
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Out of service |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
4/28/1998 |
|
Abandoned Material: |
|
| Current Age: |
29 |
|
Abandoned Date: |
|
| Install Date: |
3/14/1997 |
|
Red Tag Issue Date: |
7/14/2026 |
| Last Used Date: |
7/14/2026 |
|
Fee Due: |
$0.00 |
| Product Date: |
3/25/1997 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Composite Secondary Containment |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
5/11/2026 |
5/11/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 |
5/11/2026 |
5/11/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
5/11/2026 |
5/11/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
5/13/2024 |
5/13/2027 |
|
Piping
|
Fiberglass Chase |
Not applicable |
Not applicable |
|
Piping
|
Steel Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Double Wall STP/Tanktop Sump |
5/22/2024 |
5/22/2027 |
Leak Detect - Piping
|
Sump Sensor |
5/22/2024 |
5/22/2027 |
|
Piping
|
Single Wall STP/Tanktop Sump |
5/24/2024 |
5/26/2026 |
Leak Detect - Piping
|
Sump Sensor |
5/24/2024 |
5/26/2026 |
|
Spill Contain Device
|
Manhole Field Constructed |
5/26/2026 |
5/26/2029 |
|
Tank
|
Fiberglass Brine Filled Double Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Chase
|
Precision Test (Piping)
|
Pass
|
5/11/2026
|
|
Piping
|
Fiberglass Secondary Containment steel primary
|
Precision Test (Piping)
|
Pass
|
5/8/2020
|
|
Piping
|
Steel Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
3/24/2022
|
|
Tank
|
Fiberglass Brine Filled Double Wall
|
Precision Test (Tank)
|
Pass
|
9/8/2020
|
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors
|
Sensor Functional
|
Pass
|
7/30/2010
|
|
Leak Detect - Piping
|
Sump Sensor
|
Sensor Functional
|
Pass
|
7/30/2010
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found