Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2020652
Status: Active
Facility Name: 25112 Route 173, Inc.
Address: 25112 Route 173 Antioch, IL 60002
County: Lake
Property Parcel: 01-12-412-009
Facility Type: Attended Self-Service/Unattended Self-Service
Owner Type: Private
Green Tag Decal: AA00943
Green Tag Issue Date: 8/21/2025
Green Tag Expiration Date: 12/31/2027

Owner Details

Owner Name: 25112 Route 173, Inc.
Owner Address: 25112 Rt. 173 Antioch, IL 60002
Owner Status: Current Owner
Purchase Date: 8/1/2006
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 3/4/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 8/21/2025 12/31/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0033866 25112 Route 173, Inc. Current Owner 8/1/2006
U0032209 Combined Real Estate, LLC Former Owner 7/16/2004
U0007721 J & L Oil Co., Inc. Former Owner 12/1/1963

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
01530-2025ABN Abandon in Place Approved / Issued 11/12/2025 11/13/2025 5/13/2026 Documents
01137-2025UPG Upgrade Approved / Issued 8/22/2025 8/28/2025 3/3/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020252603 (Pending)    Issue Date: 10/3/2025    Expiration Date: 12/2/2025    View NOV Form

Tanks Violations
1 Failed to Empty the Tank to 1" or Less - Per 175.810(a)(1), when placing tanks out of service, the tank and lines must be emptied immediately. The UST is considered empty when all materials have been removed to one inch or less. Upon my inspection dated 3/18/25, I took a stick reading of the tank and it had approximately 1,548 inches of product. This tank was red tagged this date.
1 Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - This single walled tank was taken out of service on 2/1/24, and are 61 years old. Per 175.810(e) tank must be removed as it is now condemned. Here is a link to the licensed UST Decommissioning contractors, that can perform UST tank removals: https://webapps.sfm.illinois.gov/ustsearch/ContractorSearch.aspx

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 2000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/28/1986 Abandoned Material:
Current Age: 61 Abandoned Date:
Install Date: 12/1/1963 Red Tag Issue Date: 3/18/2025
Last Used Date: 2/1/2024 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 4/15/2025 4/15/2026
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 8/6/2025 8/6/2026
Overfill Prev Device Overfill Alarm 2/3/2023 2/3/2026
Overfill Prev Device Overfill Drop Tube Valve 2/28/2025 2/28/2028
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 2/28/2025 2/28/2028
Leak Detect - Piping Sump Sensor 8/6/2025 8/6/2026
Spill Contain Device Single Wall Spill Bucket 2/28/2025 2/28/2028
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 8/6/2025
Tank Steel Single Wall Precision Test (Tank) Pass 8/6/2025



Tank Number 2

Capacity: 6000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/28/1986 Abandoned Material:
Current Age: 42 Abandoned Date:
Install Date: 7/1/1983 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 4/15/2025 4/15/2026
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/6/2025 8/6/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 8/6/2025 8/6/2026
Overfill Prev Device Overfill Alarm 2/3/2023 2/3/2026
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 3/27/2025 3/27/2028
Leak Detect - Piping Sump Sensor 8/6/2025 8/6/2026
Spill Contain Device Single Wall Spill Bucket 2/28/2025 2/28/2028
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 10/8/2025
Tank Steel Single Wall Precision Test (Tank) Pass 8/6/2025



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/28/1986 Abandoned Material:
Current Age: 45 Abandoned Date:
Install Date: 10/1/1980 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 4/15/2025 4/15/2026
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/6/2025 8/6/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 8/6/2025 8/6/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Alarm 2/3/2023 2/3/2026
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 2/28/2025 2/28/2028
Leak Detect - Piping Sump Sensor 8/6/2025 8/6/2026
Spill Contain Device Single Wall Spill Bucket 2/28/2025 2/28/2028
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 8/6/2025
Tank Steel Single Wall Precision Test (Tank) Pass 8/6/2025



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/28/1986 Abandoned Material:
Current Age: 42 Abandoned Date:
Install Date: 7/1/1983 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 4/15/2025 4/15/2026
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/6/2025 8/6/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 8/6/2025 8/6/2026
Overfill Prev Device Overfill Alarm 2/3/2023 2/3/2026
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 2/28/2025 2/28/2028
Leak Detect - Piping Sump Sensor 8/6/2025 8/6/2026
Spill Contain Device Single Wall Spill Bucket 2/28/2025 2/28/2028
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 10/8/2025
Tank Steel Single Wall Precision Test (Tank) Pass 8/6/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found