Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2020652
Status: Active
Facility Name: 25112 Rt. 173, Inc.
Address: 25112 Route 173 Antioch, IL 60002
County: Lake
Property Parcel:
Facility Type: Attended Self-Service/Unattended Self-Service
Owner Type: Private
Green Tag Decal: Y001239
Green Tag Issue Date: 4/6/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: 25112 Rt. 173, Inc.
Owner Address: 25112 Rt. 173 Antioch, IL 60002
Owner Status: Current Owner
Purchase Date: 8/1/2006
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 3/4/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 4/6/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0033866 25112 Rt. 173, Inc. Current Owner 8/1/2006
U0032209 Combined Real Estate, LLC Former Owner 7/16/2004
U0007721 J & L Oil Co., Inc. Former Owner 12/1/1963

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020243255 (Referred to Legal)    Issue Date: 12/16/2024    Expiration Date: 2/14/2025    View NOV Form

Tanks Violations
1 Submit Notification Form For Tank Status Change - Submit OSFM Notification Form placing tanks in Out of Service status. The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm.
1, 2, 3, 4 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Only Tank 2 not tested.

NOV Number: E0020251520 (Pending)    Issue Date: 6/16/2025    Expiration Date: 8/15/2025    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2, 3, 4 Annual leak detection certification not completed (Required annually).
2, 3, 4 Annual line precision and mechanical line leak detector functional test not completed.
Facility Due to a red tagged tank(s) at this facility, after 60 days from the issuance date of this NOV, in the absence of full compliance, all tanks shall be red tagged - Diesel tank (Tank 2) is currently red tagged.
1 Failed to Empty the Tank to 1" or Less - Tank is red tagged and out of service.
2, 3, 4 Flex connector damaged or worn - replace flex connector and precision test line - Dispenser 7/8 Flex connector damaged.
1, 2, 3, 4 Line interstitial sensor functional test not accomplished (Required annually). - STP sensor testing not completed.
3 Line leak detection equipment in alarm or failed test, must repair or replace. - L1: Prem STP Fuel Alarm
Facility Miscellaneous - Emergency stop shall be readily accessible and conspicuously marked by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters. (Per 41 Ill Admin code 175.210(d)(3))
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom.
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing list of designated Class A/B & C Operators
1, 2, 3, 4 Monthly impressed current system log not available or maintained. - A log showing the rectifier gauge readings from Impressed Current rectifier shall be maintained monthly on site. Log shall show date; amp, volt, and hour meter readings; including the initials of the employee who recorded information.
1, 2, 3, 4 Monthly line interstitial sensor records not available.
1, 2, 3, 4 Required monthly tank leak test records not available.
1, 2, 3, 4 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
1, 2, 3, 4 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1, 2, 3, 4 Tank precision test required. - Precision tank test is required due to missing or failed monthly monitoring (Per 41 Ill Admin code 175.630(c)(2))

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 2000 Diesel Fuel Out of service Federal 3/18/2025 $0.00
2 6000 Gasoline - Regular Currently in use Federal $0.00
3 10000 Gasoline - Premium Currently in use Federal $0.00
4 10000 Gasoline - Regular Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found