Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2020404
Status: Active
Facility Name: Minuteman CITGO
Address: 402 Plainfield Road
Darien, IL 60561
County: Du Page
Property Parcel: 09-27-206-009
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X000653
Green Tag Issue Date: 12/15/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Infinity Sales
Owner Address: 402 West Plainfield Road
Darien, IL 606514208
Owner Status: Current Owner
Purchase Date: 12/8/2004
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 10/5/2023

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 5/25/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0033234 Infinity Sales Current Owner 12/8/2004
U0014941 Texor Petroleum Company, Inc. Former Owner 6/29/1994
U0008192 Kean Oil Company Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241276 (Pending)    Issue Date: 4/24/2024    Expiration Date: 6/23/2024    View NOV Form

Tanks Deficiency
Facility A/B operator retraining required as a result of issuance of the Notice of Violation - Operators working with no class C certificate
Facility Facility Operation and Maintenance Plan not completed or available.
Facility Financial responsibility must be reported yearly
Facility Missing copies of Annual Walkthrough Inspection Report. - Completed by your contractor
Facility Missing copy of emergency instructions or emergency procedures plan
Facility Missing list of designated Class A/B & C Operators - Must update with current employees
1, 2, 3, 5 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
Facility Submit Notification Form For Ownership Change

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
93-2338 Eligible 1/19/1994 1/26/1994 $15,000
94-1805 Eligible 5/16/1995 6/2/1995 $15,000
05-1400 Eligible 6/9/2006 7/5/2006 $15,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 6000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 50 Abandoned Date:
Install Date: 6/1/1974 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 12/13/2022 12/13/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Other Non-vented check valve N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 7/12/2023 7/12/2024
Overfill Prev Device Overfill Drop Tube Valve 7/28/2021 7/28/2024
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 7/28/2021 7/28/2024
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test Pass 8/20/2021
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 3/25/2010



Tank Number 2

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 50 Abandoned Date:
Install Date: 6/1/1974 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 12/13/2022 12/13/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 7/12/2023 7/12/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 7/12/2023 7/12/2024
Overfill Prev Device Overfill Drop Tube Valve 11/2/2022 11/2/2025
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 7/28/2021 7/28/2024
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test Pass 8/8/2019
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 3/25/2010



Tank Number 3

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 50 Abandoned Date:
Install Date: 6/1/1974 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 12/13/2022 12/13/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 7/12/2023 7/12/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 7/12/2023 7/12/2024
Overfill Prev Device Overfill Drop Tube Valve 7/28/2021 7/28/2024
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 7/28/2021 7/28/2024
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 3/25/2010



Tank Number 4

Capacity: 500 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/9/1994
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 6/1/1974 Red Tag Issue Date:
Last Used Date: 5/9/1994 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/9/1993 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 6/15/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 9/30/2022 9/30/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 7/12/2023 7/12/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 7/12/2023 7/12/2024
Overfill Prev Device Overfill Drop Tube Valve 7/28/2021 7/28/2024
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 7/28/2021 7/28/2024
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test Pass 8/20/2021
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 3/25/2010



Tank Number 6

Capacity: 500 Petroleum Use: Consumptive Use on Premises for Heating
Product: Heating Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: State Removed Date: 5/9/1994
OSFM First Notify Date: 3/29/1994 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 6/1/1974 Red Tag Issue Date:
Last Used Date: 1/1/1976 Fee Due: $0.00
Product Date: 6/1/1974

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found