| 6, 7 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Section 175.410 Submersible, Under-dispenser, Transition and Other Containment Sumps
a) All containment sumps must consist of a factory manufactured containment that is liquid-tight on its sides, bottom and at any penetrations and is compatible with the substance conveyed by the piping. Such containment shall also have a factory manufactured protective cover and supporting components that are properly maintained. If the protective cover or its supporting components are cracked, deteriorated, or missing, the cover and supporting components that are defective shall be replaced. SPECIFICALLY, THE STP HANDLES ARE MISSING/CORRODED OFF. |
| Facility |
Financial responsibility must be reported yearly - Financial Responsibility shall be declared annually, and must be maintained until the tanks are removed or properly abandoned in place by a licensed UST decommissioning contractor. The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility. |
| 6, 7, 8 |
Piping interstitial must be open in all sumps - Remove all jumper tubing/pull back test boots for piping interstitial. 175.420 b. SPECIFICALLY DISPENSER 1/2 AND 3/4. |
| 7 |
Tank interstitial sensors in alarm or failed test, must repair or replace. - Interstitial sensor in failed test 3/3/2025; Repair/replace sensor as necessary and upload passing results to OSFM website. |