Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2020339
Status: Active
Facility Name: 8596 DG Mart, Inc.
Address: 8596 W. Dempster Niles, IL 60714
County: Cook
Property Parcel: 09-14-309-011-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003297
Green Tag Issue Date: 12/26/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: DG Mart Real Estate, Inc.
Owner Address: 8596 W. Dempster Niles, IL 60714
Owner Status: Current Owner
Purchase Date: 8/16/2016
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 11/9/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 12/26/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038436 DG Mart Real Estate, Inc. Current Owner 8/16/2016
U0035189 PAV 2, LLC, Former Owner 7/12/2012
U0035854 First Merit Bank (formerly Midwest Bank & Trust) Former Owner 9/29/2009
U0035789 Midwest Bank and Trust Company Former Owner 9/29/2009
U0033815 Rahim, Anwar Former Owner 10/13/2006
U0027493 Amoco Oil Company Former Owner 1/1/1984
U0000552 BP Products North America, Inc. Former Owner 1/1/1984

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252807 (Pending)    Issue Date: 10/22/2025    Expiration Date: 12/21/2025    View NOV Form

Tanks Violations
Facility Financial responsibility must be reported yearly - Per 176.220, tank owners/operators must submit and electronic Financial Responsibility (FR) Report form on an annual basis and at time of ownership change. FR must be maintained until the tanks is either removed or properly abandoned in place by a licensed UST decommissioning contractor. Here is the link to the electronic Financial Responsibility Report form: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility
Facility Submit Notification Form For Ownership Change - Per 41 Ill. Adm. Code 176.440 (g), a change of ownership information must be reported on an electronic Notification for Underground Storage Tank form, within 30 days of the change. According to the Cook County Clerk’s Recorder of Deeds Office, a Warranty Deed was filed on 11/15/24. The Notification Form is available at: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm.

NOV Number: E0020252808 (Pending)    Issue Date: 10/22/2025    Expiration Date: 12/21/2025    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers.

NOV Number: E0020252809 (Pending)    Issue Date: 10/22/2025    Expiration Date: 12/21/2025    View NOV Form

Tanks Violations
6, 7 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Section 175.410 Submersible, Under-dispenser, Transition and Other Containment Sumps a) All containment sumps must consist of a factory manufactured containment that is liquid-tight on its sides, bottom and at any penetrations and is compatible with the substance conveyed by the piping. Such containment shall also have a factory manufactured protective cover and supporting components that are properly maintained. If the protective cover or its supporting components are cracked, deteriorated, or missing, the cover and supporting components that are defective shall be replaced. SPECIFICALLY, THE STP HANDLES ARE MISSING/CORRODED OFF.
Facility Financial responsibility must be reported yearly - Financial Responsibility shall be declared annually, and must be maintained until the tanks are removed or properly abandoned in place by a licensed UST decommissioning contractor. The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility.
6, 7, 8 Piping interstitial must be open in all sumps - Remove all jumper tubing/pull back test boots for piping interstitial. 175.420 b. SPECIFICALLY DISPENSER 1/2 AND 3/4.
7 Tank interstitial sensors in alarm or failed test, must repair or replace. - Interstitial sensor in failed test 3/3/2025; Repair/replace sensor as necessary and upload passing results to OSFM website.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
14-0738 12/8/2015 Removal Log 01005-2015REM
14-0738 12/11/2015 Removal Log 01005-2015REM
14-0738 12/15/2015 Removal Log 01005-2015REM
94-0417 5/31/1994 Removal Log

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
94-0417 Eligible 7/25/1996 8/23/1996 $10,000
09-1446 Eligible 4/14/2010 5/24/2010 $10,000
09-1446 Eligible 1/10/2013 1/29/2013 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 12000 Gasoline Removed Federal $0.00 12/15/2015 - REM
2 12000 Gasoline Removed Federal $0.00 12/11/2015 - REM
3 12000 Gasoline Removed Federal $0.00 12/11/2015 - REM
4 550 Used Oil Removed Federal $0.00 01/01/1993 - REM
5 550 Used Oil Removed Federal $0.00 12/08/2015 - REM
6 12000 Gasoline - Regular Currently in use Federal $0.00
7 6000 Gasoline - Premium Currently in use Federal $0.00
8 8000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
2020339 8596 DG Mart, Inc. Niles 12/12/2016 Letter Form