Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2020322
Status: Active
Facility Name: BP - Shop
Address: 520 South Austin
Oak Park, IL 60304
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002426
Green Tag Issue Date: 1/2/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: K B J, Inc.
Owner Address: 520 South Austin
Oak Park, IL 60304
Owner Status: Current Owner
Purchase Date: 11/30/2007
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 11/29/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 2/20/2025 12/31/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0034546 K B J, Inc., Current Owner 11/30/2007
U0000552 BP Products North America, Inc. Former Owner 1/1/1977

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
01545-2024UPG Upgrade Approved / Issued 12/2/2024 12/2/2024 6/3/2025 Documents

Notice of Violations (Current)

NOV Number: E0020250430 (Pending)    Issue Date: 2/20/2025    Expiration Date: 4/21/2025    View NOV Form

Tanks Violation
Facility Financial responsibility must be reported yearly
4, 5, 6 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
4 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - DIESEL STP IS FULL OF WATER

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
91-0747 Eligible 11/9/1998 12/24/1998 $10,000
89-0797 Eligible 11/9/1998 12/24/1998 $50,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 1/1/1986
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 4/30/1965 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 1/1/1986
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 4/30/1965 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 1/1/1986
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 4/30/1965 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 48 Abandoned Date:
Install Date: 4/30/1977 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/30/1977

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/14/2024 11/14/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 11/14/2024 11/14/2025
Overfill Prev Device Overfill Drop Tube Valve 11/14/2024 11/14/2027
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 11/14/2024 11/14/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 9/30/2020 9/30/2021
Leak Detect - Piping Sump Sensor 11/14/2024 11/14/2025
Spill Contain Device Single Wall Spill Bucket 11/14/2024 11/14/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 8/10/2021



Tank Number 5

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/23/1993 Abandoned Material:
Current Age: 38 Abandoned Date:
Install Date: 7/14/1986 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/14/1986

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Sacrificial Anode Cathodic Protection 10/25/2023 10/25/2026
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/14/2024 11/14/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 11/14/2024 11/14/2025
Overfill Prev Device Overfill Drop Tube Valve 12/19/2024 12/19/2027
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 11/14/2024 11/14/2027
Leak Detect - Piping Sump Sensor 11/14/2024 11/14/2025
Spill Contain Device Double Wall Spill Bucket 12/19/2024 12/19/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 8/10/2021



Tank Number 6

Capacity: 10000 Petroleum Use: None
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/23/1993 Abandoned Material:
Current Age: 38 Abandoned Date:
Install Date: 7/14/1986 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/14/1986

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Sacrificial Anode Cathodic Protection 10/25/2023 10/25/2026
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/14/2024 11/14/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 11/14/2024 11/14/2025
Overfill Prev Device Overfill Drop Tube Valve 11/14/2024 11/14/2027
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 11/14/2024 11/14/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 9/30/2020 9/30/2021
Leak Detect - Piping Sump Sensor 11/14/2024 11/14/2025
Spill Contain Device Single Wall Spill Bucket 11/14/2024 11/14/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 12/2/2019

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/5/2024 12/5/2027
Leak Detect - Piping Sump Sensor 11/14/2024 11/14/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 11/14/2024 11/14/2027
Leak Detect - Piping Sump Sensor 11/14/2024 11/14/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/5/2024 12/5/2027
Leak Detect - Piping Sump Sensor 11/14/2024 11/14/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/5/2024 12/5/2027
Leak Detect - Piping Sump Sensor 11/14/2024 11/14/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/5/2024 12/5/2027
Leak Detect - Piping Sump Sensor 11/14/2024 11/14/2025

MFD Motorfuel Dispensing Forms

No Forms Found