Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2020307
Status: Active
Facility Name: C & C Trading Group, Inc.
Address: 1520 Big Timber Rd.
Elgin, IL 60123
County: Kane
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001651
Green Tag Issue Date: 1/4/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: C & C Trading Group, Inc.
Owner Address: 1520 Big Timber Rd.
Elgin, IL 60123
Owner Status: Current Owner
Purchase Date: 12/28/2016
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 8/28/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/4/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038676 C & C Trading Group, Inc. Current Owner 12/28/2016
U0036179 MVQ Corporation Former Owner 6/30/2011
U0034299 M.V.P. Corporation Former Owner 12/31/2006
U0031777 John, John Former Owner 9/23/2003
U0023834 BP Amoco Former Owner 4/8/1995
U0027493 Amoco Oil Company Former Owner 1/1/1991
U0000552 BP Products North America, Inc. Former Owner 1/1/1991
U0035571 Big Timer Real Estate LLC Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250704 (Pending)    Issue Date: 3/18/2025    Expiration Date: 5/17/2025    View NOV Form

Tanks Violation
5, 6, 7 Annual electronic line leak detector test not completed. - Annual leak detection certification (leak detectors) not completed. Testing shall be performed.
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain 2 years on site with other annual testing documentation.
5, 6, 7 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (ATG) not completed. Testing shall be completed and submitted to OSFM.
Facility Miscellaneous - REGULAR ATG RISER CAP IS NOT PROPERLY SECURED ON RISER, IT WAS HANGING OFF TO THE SIDE.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and 2 years of documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and 2 years documentation maintained on site.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures plan shall be maintained on site for viewing and reference as necessary (See Operator Training Rules 176.645). The emergency plan template is available on the OSFM website.
5, 6, 7 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Must maintain 2 years of inspection reports.
5, 6, 7 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
5, 6, 7 Tank monitor does not appear to function properly and requires maintenance. - Indicator Green light on panel of Veeder-Root ATG is not functional. Replace as necessary to provide proper operation.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
90-3209 7/12/1991 Removal Log
92-3209 7/12/1991 Removal Log

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline Removed Federal $0.00 07/11/1991 - REM
2 10000 Gasoline Removed Federal $0.00 07/11/1991 - REM
3 6000 Gasoline Removed Federal $0.00 07/11/1991 - REM
4 550 Used Oil Removed Federal $0.00 07/11/1991 - REM
5 12000 Gasoline - Regular Currently in use Federal $0.00
6 12000 Gasoline - Premium Currently in use Federal $0.00
7 12000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found