Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2020304
Status: Active
Facility Name: Mobil Gas Station
Address: 251 West 63rd Street
Chicago, IL 60621
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001426
Green Tag Issue Date: 4/7/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Northern Associates, Inc.
Owner Address:
Owner Status: Current Owner
Purchase Date: 1/1/2005
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/23/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 4/7/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0032758 Northern Associates, Inc. Current Owner 1/1/2005
U0023834 BP Amoco Former Owner 4/24/1998
U0000926 Atlantic Richfield Co Former Owner 4/10/1995
U0027493 Amoco Oil Company Former Owner 1/1/1991
U0000552 BP Products North America, Inc. Former Owner 1/1/1991
U0032858 South Bound Food, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020251270 (Pending)    Issue Date: 5/14/2025    Expiration Date: 7/13/2025    View NOV Form

Tanks Violation
4, 5, 6 Overfill prevention equipment inspection(s) not completed (Required every 3 years).
4, 5, 6 Piping sacrificial anode system not tested (required every 3 years).
5, 6 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
4, 5, 6 Tank sacrificial anode system not tested (Required every 3 years).
4, 5, 6 Triennial spill prevention equipment testing not completed.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
91-2251 Eligible 7/30/1998 9/1/1998 $10,000
04-1275 Eligible 12/21/2004 1/11/2005 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/1/1991
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 1/1/1968 Red Tag Issue Date:
Last Used Date: 8/1/1991 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/1/1991
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 1/1/1968 Red Tag Issue Date:
Last Used Date: 8/1/1991 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/1/1991
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 1/1/1968 Red Tag Issue Date:
Last Used Date: 8/1/1991 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/24/1992 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 4/1/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 4/13/2022 4/13/2025
Corrosion Prot - Tank Sacrificial Anode Cathodic Protection 4/13/2022 4/13/2025
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 1/9/2025 1/9/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 1/9/2025 1/9/2026
Overfill Prev Device Overfill Drop Tube Valve 4/13/2022 4/13/2025
Piping Steel Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 4/13/2022 4/13/2025
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Steel Single Wall Piping Precision Test (Piping) Pass 1/9/2025



Tank Number 5

Capacity: 12000 Petroleum Use:
Product: Gasoline - Mid-grade CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/24/1992 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 4/1/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 4/13/2022 4/13/2025
Corrosion Prot - Tank Sacrificial Anode Cathodic Protection 4/13/2022 4/13/2025
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 1/9/2025 1/9/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 1/9/2025 1/9/2026
Overfill Prev Device Overfill Drop Tube Valve 4/13/2022 4/13/2025
Piping Steel Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 4/13/2022 4/13/2025
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Steel Single Wall Piping Precision Test (Piping) Pass 1/9/2025



Tank Number 6

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/24/1992 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 4/1/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 4/13/2022 4/13/2025
Corrosion Prot - Tank Sacrificial Anode Cathodic Protection 4/13/2022 4/13/2025
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 1/9/2025 1/9/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 1/9/2025 1/9/2026
Overfill Prev Device Overfill Drop Tube Valve 4/13/2022 4/13/2025
Piping Steel Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 4/13/2022 4/13/2025
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Steel Single Wall Piping Precision Test (Piping) Pass 1/9/2025



Tank Number 7

Capacity: 550 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 10/1/1985
OSFM First Notify Date: 4/28/1986 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 1/1/1978 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found