Notice of Violations (Current)
NOV Number:
E0020250656
(Pending)
Issue Date:
3/13/2025
Expiration Date:
5/12/2025
View NOV Form
Tanks |
Violation |
6, 7, 8 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). |
7, 8 |
Tank monitor does not appear to function properly and requires maintenance. - Gasoline tanks are not passing CSLD tests. Need to get permit to remove as testing method or close pumps long enough to pass test. Veeder Root should not be in constant alarm because station is busy. |
6, 7, 8 |
Triennial spill prevention equipment testing not completed. |
6, 7, 8 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Dispenser and submersible sumps are overdue for 3 year test. |