Notice of Violatlions (Current)
NOV Number:
E0020261467
(Pending)
Issue Date:
6/4/2026
Expiration Date:
8/3/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser - Attendant does not have an unobstrcted view of all dispensers. |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable |
| Facility |
Fire Extinguishers - 2 4A:60BC extinguishers not provided, 1 at or near control station and 1 in the dispensing areas - No fire extinguishers available. |
NOV Number:
E0020261471
(Pending)
Issue Date:
6/4/2026
Expiration Date:
8/3/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Facility Operation and Maintenance Plan not completed or available. - Form available at:
https://sfm.illinois.gov/about/divisions/petroleum-chemical-safety/applications-and-forms.html |
| Facility |
Missing copies of 30 day Walkthrough Inspection Report. - Form available at:
https://sfm.illinois.gov/about/divisions/petroleum-chemical-safety/applications-and-forms.html |
| Facility |
Missing copies of Annual Walkthrough Inspection Report. - Form available at:
https://sfm.illinois.gov/about/divisions/petroleum-chemical-safety/applications-and-forms.html |
| Facility |
Missing list of designated Class A/B & C Operators - Form available at:
https://sfm.illinois.gov/about/divisions/petroleum-chemical-safety/applications-and-forms.html |
| 5, 6, 7, 8 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Liquid in all spill buckets. |
| 5, 6, 7, 8 |
Tank monitor does not appear to function properly and requires maintenance. - No power to veeder root. |