| 4, 5 |
Failed to Empty the Tank to 1" or Less - Per 175.810(a) (1), when placing tanks out of service, the tanks and lines must be emptied immediately. The UST is considered empty when all materials have been removed to one inch or less. As of 10/15/2026, tank 4 has 3,215 gallons or approximately 64 inches of product and tank 5 has 86 gallons or approximately 6.23 inches of product in the tank, as confirmed by the automatic tank gauge. |
| 4, 5 |
Submit Notification Form For OOS Tank Status Change - Per 175.810(a) (3), tanks taken out of service are required to notify the OSFM within 30 days of the date of last use, on an electronic Notification for Underground Storage Tank form, declaring a tank status change. These tanks have been out of service since 8/5/2026 for repair to the interstitial monitoring, thus far no repairs have been made. Here is the link to the electronic Notification for Underground Storage Tank form, so you can file that change: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. |