Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2018734
Status: Active
Facility Name: Northern Illinois Medical Center
Address: 4201 Medical Center Drive McHenry, IL 60050
County: McHenry
Property Parcel:
Facility Type: Private Institution
Owner Type: Private
Green Tag Decal: Z003734
Green Tag Issue Date: 1/30/2024
Green Tag Expire Date: 12/31/2026
MFD Type: N/A

Owner Details

Owner Name: Northern Illinois Medical Center
Owner Address: 10400 Haligus Rd. Huntley, IL 60142
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 11/25/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0011008 Northern Illinois Medical Center Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

No Notice of Violations Found

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/26/1986 Abandoned Material:
Current Age: 41 Abandoned Date:
Install Date: 8/26/1985 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 1/20/2025 1/20/2028
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 1/20/2025 1/20/2028
Leak Detect - Piping American with Annual Prec Line Testing Suction 1/5/2026 1/5/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 4B 3/9/2026 3/9/2027
Overfill Prev Device Overfill Drop Tube Valve 1/20/2025 1/20/2028
Piping Steel Single Wall Piping Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 1/5/2026 1/5/2029
Tank STIP3 Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Steel Single Wall Piping Precision Test (Piping) Pass 1/5/2026
Tank STIP3 Single Wall Precision Test (Tank) Pass 10/22/2024



Tank Number 2

Capacity: 5000 Petroleum Use:
Product: Salt Brine CERCLA Substance:
Status: Unknown CAS Code:
Regulated Status: Non-Regulated Removed Date:
OSFM First Notify Date: 3/26/1986 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment Information

No Equipment Listed


Additional Tests

No Tests Listed




Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Jet A CERCLA Substance:
Status: Does Not Exist CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment Information

No Equipment Listed


Additional Tests

No Tests Listed


Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


Dispenser Information




Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


MFD Motorfuel Dispensing Forms

No Forms Found